T & R 100 ADM Main Output
The main output on the unit has four taps, allowing the selection of output voltages up to 240V and output currents up to 200A.
|
|
Current
|
Output @230V
|
|
Range
|
Continuous
|
5 min*
|
1 min*
|
|
O/CV
|
Load V
|
|
10V
|
33A
|
67A
|
100A
|
|
10.6V
|
8.7V@100A
|
|
35V
|
10A
|
20A
|
30A
|
|
36V
|
32V@30A
|
|
100V
|
3A
|
6A
|
10A
|
|
108V
|
99V@10A
|
|
240V
|
1A
|
2A
|
3A
|
|
276V
|
259V@3A
|
|
240Vdc
|
1A
|
2A
|
3A
|
|
|
|
*Off time of 15 minutes. On times based on an ambient temperature of 25°C.
Protection: over current trip, duty cycle trip, thermal monitoring.
I Limit Mode
The main output has a current limit mode that gives very fine control of output currents up to 10A. It also allows fine current control into very low impedance loads such as digital relays.
|
|
Current
|
Output @230V
|
|
Range
|
Short Circuit
|
Continuous
|
5min
|
2min
|
O/CV
|
Load V
|
|
10V
|
10A
|
3A
|
6A
|
10A
|
8.6V
|
5V@6A
|
|
35V
|
3A
|
1A
|
2A
|
3A
|
29V
|
132V@30A
|
|
100V
|
1A
|
0.3A
|
0.6A
|
1A
|
88V
|
99V@10A
|
|
240V
|
0.3A
|
0.1A
|
0.2A
|
0.3A
|
224V
|
259V@3A
|
Auxiliary DC Output
|
Range
|
Maximum A
|
Continuous Rating
|
|
24V
|
1A
|
25W
|
|
48V
|
1A
|
25W
|
|
60V
|
1A
|
25W
|
|
110V
|
0.23A
|
25W
|
|
220V
|
0.23A
|
25W
|
Protection: current limit
Fixed AC Output
|
Output Voltage
|
Current
|
|
110V
|
|
300mA
|
Protection: fuse.
Metering
The 100ADM output is metered by a digital true RMS system with a single cycle capture memory ammeter—whenever the timer stops and the output is switched off, the current reading is held on the display. The RMS value of a single cycle can be captured. A current trip is set to 110% of full scale of the selected metering range.
|
Range
|
Resolution
|
Trip
current
|
Accuracy
|
Aquisition
time
|
|
2.000A
|
0.001A
|
2.1A
|
±0.5% rdg±5d
|
20ms
|
|
10.00A
|
0.01A
|
10.5A
|
±0.5% rdg±5d
|
20ms
|
|
20.00A
|
0.01A
|
21A
|
±0.5% rdg±5d
|
20ms
|
|
100.0A
|
0.1A
|
105A
|
±0.5% rdg±5d
|
20ms
|
Timing System
| Range |
0-999.999s/9999.99s/99999.9s autoranging |
| Resolution |
1/10/100ms |
| Accuracy |
0.01%rdg+2d (+4d current operated mode) |
| Contact o/c |
24V |
| Contact s/c |
20mA |
| Vdc |
24—240V |
Each contact circuit will auto-select for normally open or normally closed contacts. A DC voltage of 24—240Vdc may also be used to trigger either timer channel. Contact state is shown by an LED.
Supply Requirements
115V/230V ±10% auto-selecting 50/60Hz 1ph 1100VA max.
Safety
An earth terminal is provided for connection to a local earth. The unit is designed to comply with BSEN61010 and is CE marked.
Temperature Range
Storage -20°C to 60°C
Operating 0°C to 45°C
Standard Accessories
The T and R 100ADM mk4 is supplied with operating manual, mains lead and, output lead set and spare fuses.
Optional Accessories
100ADM-F filter unit, RB10 resistor box, printer kit, ADMlog software.
The unit is supplied as standard in an aluminium case with removable lid. The unit is also available in a plastic Pelicase as an option. Please note that the Pelicase lid is not removable and opens as far as shown in the picture below.
Weights and Dimensions
| T and R 100ADM |
Dimensions |
Weight |
| Standard unit |
380mm x 314mm x 221mm |
19.5kg |
| Pelicase unit |
560mm x 456mm x 265mm |
23.3kg |