The new Megger MFT1710 Multifunction Tester for all 17th Edition and Part P testing applications on low voltage, fixed electrical installations. The Megger MFT 1710 is a great electrical installation tester for electricians who want to test, certify or fault find on domestic and commercial properties. Tests included are supply measurement, continuity, insulation, loop and RCD testing. The MFT1710 multi-function tester has been designed to continue working when connected across phases, when connected to a live circuit and when the incorrect range is selected making this one of the most reliable testers on the market.
The MFT 1710 has a balanced neckstrap for hands-free operation with a TEST button on both ends of the tester for either left or right-handed testing. The large character dual display with backlight allows for two parameters to be shown at one time and colour coded range selection dials make this an intuitive and straightforward multifunction tester to use. The rugged design and IP54 rated rubber moulding of the MFT1710 allow the instrument to withstand tough conditions and heavy handed treatment. Together with a CAT IV 300V safety rating the Megger 1710 is a 17th Edition tester designed for safe using either inside or out. The carry case for this new Megger 17th Edition tester ensures the safe transportation of the instrument when travelling between tests and has extra space for the storage of tools, test leads and a certificate pad.
Megger MFT1710 Multifunction Tester features
► Insulation testing at 250V and 500V
► 200mA Continuity test
► 2-wire no-trip & high current loop testing
► Polarity test
► RCD ramp test
► Auto-start tests on continuity and loop resistance – no need to push the button
► Dual display shows loop resistance and fault current results simultaneously
► Dual test buttons for left or right-handed operation
► Test lockout
► Safe contact detector
► Live circuit warning
► Auto discharge
► Analogue arc display
► Weatherproof to IP54
► Input protection against accidental connection to live circuits
► CAT IV 300V safety standard
Other models in the new MFT1700 series for your comparison
► For the MFT1720 click here
► For the MFT1730 click here
► For the MFT1730 OnSite click here
► Megger MFT1710 Multifunction 17th Edition Tester
► MFT 1710 user guide
► 3-wire test lead set with croc clips
► Mains plug test lead
► Neck strap
► Quick-start guide
► Hard carry-case
► 8 x AA batteries
► FREE Calibration Certificate
► Manufacturers 3 year warranty
► FREE CalBox Calibration Checker
If you require a detailed specification please see the Megger MFT1700 Series pdf ![]()
Insulation test
► Output voltage: -0% +20% at rated load or less
► Voltage display: ±3% ±3 digits ±0.5% of rated voltage
► Short circuit current: 1.5 mA nominal test current
► Test current on load: 1 mA at min pass values of insulation
Measurement accuracy
► 500V: 10kΩ ~ 500MΩ ±3% ±2 digits, >500MΩ ±10% ±4 digits
► 250V: 10kΩ ~ 250MΩ ±3% ±2 digits, >250MΩ ±10% ±4 digits
Continuity / resistance
► 0.01Ω ~ 99.9Ω: ±2% ±2 digits
► 100Ω ~ 99.9kΩ: ±5% ±2 digits
► Open circuit voltage: 5V ±1V
► Test current(0Ω ~ 2Ω): 205mA ±5mA, 15mA ±5mA(user selectable)
Loop test
► Live to earth supply: 48V ~ 280V (45Hz ~ 65Hz)
► Live to live supply: 48V ~ 480V (45Hz ~ 65Hz)
► L-E tests: ±5% 0.05Ω ±Noise margin
► L-N/L-E tests: ±5% ±0.03Ω
► Display range: 0.01Ω ~ 1000Ω
► Live to earth PFC range: 20kA
► Live to live PSCC range: 20kA
RCD tests
► Supply up to 100mA: 48V ~ 480V (45Hz ~ 65Hz)
► Supply up to 1A: 48V ~ 280V
► RCD type: Type AC, A, S
► No trip test (1/2xI): –10% ~ 0%
► Trip test (1xI, 2xI & 5xI): 0% ~ 10%
RCD Ramp test
► Touch voltage (0 ~ 253V): +5% +15% ±0.5V
► Trip time: ±1% ±1ms
► Trip current: ±5%
VAR (variable RCD selection)
► 10mA ~ 50mA, 1mA steps.
► 50mA ~ 500mA, 5mA steps
Supply measurement
► Voltage: 10V ~ 600V (15 ~ 400Hz), ±3% ± 1V ±2 digits
► Phase rotation indication: L1–L2–L3 & L1–L3–L2
► Frequency: 15Hz ~ 99Hz ±0.5% ±1 digit, 100Hz ~ 400Hz ±2.0% ±2 digit
► Frequency resolution: 0.1Hz
Current (via optional clamp meter)
► Range: 0.1mA to 200A AC
► Resolution: 0.1mA
Safety
► IEC 61010-1:2010
► IEC 61010-30:2010
► IEC 61010-031:2008
► 600 V Cat III / 300 V Cat IV (Max Phase to Phase 600 V)
► IEC 61557:2007 parts 1 to 10
► IEC61326 edition 2 location class B
► Temperature (operational): -10°C ~ 55°C
► Temperature (storage): -25°C ~ 70°C
► Operating humidity: 90% R.H. at 40°C max
► Max altitude: 2000m
► Weight: 1kg
► Moisture/dust ingress protection: IP54
► Power: IEC LR6 type AA alkaline (6 cells - supplied)