PRODUCT SPECIFICATIONS:
► Input Voltage: 3 x 0-480 Vac Inline shrouded 4mm banana plugs & fused croc clip
► Input Currents: 3 x 24" 1000A Flexible Current Clamps or 0-.5 Vac current clamp voltage output
► Accuracy: Volts & Wide range current <0.25% True RMS. Narrow range current <1% True RMS
► Resolution: Programmable to 0.1 Vac & 0.1 Aac 0.01V, 0.01A high resolution mode
► Maths Channels:
AC 1 Phase: RMS, Stray Voltage RMS Hi Res <35V, Real power, VARS (fund), Apparent Power, Power Factor, Phase angle, Frequency.
AC 2 Phase: Real Power, VARS (fund), Apparent Power, Power Factor.
AC 3 Phase: Real Power, VARS (fund), Apparent Power, Power Factor, Voltage Unbalance, Current Unbalance (Conventional & Sequential Components)
Harmonics: Total Harmonics Value, % Total Harmonic Distortion.
Other Maths Option: Channel X* Constant, Channel X / Channel Y, Filtered Channel X, Internal Temperature, On Charge, Battery Volts.
► Recording: 64 samples per cycle; single cycle True RMS response time; 16 bit simultaneously sampling all channels
► Recording Mode and Rate:
Adaptive Store: Unique store management enables extended recording & single cycle resolution on significant signal changes.
Point Store: Selectable from single cycle rate to once every 12 hours
► Power: Requires 50-480 Vac off of Phase A voltage measurement or seperate power supply
► Memory: 1mB RAM
► Safety & Standards: IEC 61010, CE, IEC 61326 (EMC), IEC 61000-4-15
► Case: Pelican 1120 Guard Box: Dimensions 8" x 6.5" x 3.5"
► Weight: 2.5lbs. without leads & clamps
► Computer requirements for Software: Windows 98, ME, NT4, 2000, Pentium processor, XP: 32MB RAM