Buy Now
Primary injection upto 5000A, secondary injection upto 100A

More images...

Be the first to review this product!

Product Features: T&R PCU1-SP Primary Current Injection Test System

T&R PCU1-SP mk2 Primary Current Injection System

The PCU1-SP Primary Current Injection Test System is ideally suited to primary current injection, stability testing and circuit breaker testing, offering a current output up to 5000A with the necessary loading unit. In addition the PCU1-SP version offers direct-reading CT ratio and polarity tests and a 100A secondary injection input. The system consists of a separate control unit containing all metering and control functions and a loading unit that provides the high current output. There is a choice of two loading units to accompany the PCU1-SP control unit that are necessary to provide the high current output. The NLU2000 delivers a maximum output current of 2000A, while the NLU5000 offers a maximum output current of 5000A. Each of the loading units has three output taps to allow for a wide range of load impedances. For example, the NLU5000 may be configured to either give a maximum current of 5000A on the 2.3V range, 2500A on the 4.6V range or 1250A on the 9.2V range.

The T&R PCU1 control unit is rated at 11.5kVA with a 2 second overload capability of 23kVA when using the pulse mode. All metering is digital and a memory facility is provided to hold the current reading when the output trips or is switched off. The current is thyristor controlled and is automatically switched off when the load being tested, trips. The PCU1-SP system has a high accuracy timing system, allowing timing tests to be carried out to a resolution of 1ms. Normally open or normally closed contact selection is automatic with the status of the contacts shown on the front panel. The flexible timing system has two contact inputs and five operating modes that are available to test under and over current devices, re-closers, under and over voltage devices, current trips and circuit breakers.

PCU1-SP Primary Current Injection features
5kA maximum output current (higher overload currents for 2s)
Secondary injection up to 100A
Direct reading CT ratio and polarity
Multi-function digital timing system
Digital true RMS memory ammeter
Solid state switching
Choice of 2000A and 5000A loading units
Three range outputs on loading units
Rugged, compact design
Optional trolley mounting of system

To purchase a necessary loading unit to accompany the PCU1-SP please visit either the NLU2000 or NLU5000 product page.

Supplied Accessories: T&R PCU1-SP Primary Current Injection Test System

T&R PCU1-SP control unit
5m mains lead
5m loading unit power and metering leads
Spare fuses
Operating manual

Product Specifications: T&R PCU1-SP Primary Current Injection Test System

Load Unit Current Metering (NLU2000)

Range Full scale Resolution Accuracy
10% 200A 0.1A ±0.5%rdg+5d
50% 1000A 1A ±0.5%rdg+5d
100% 2000A 1A ±0.5%rdg+5d
200% 4000A 1A ±1%rdg+5d

Load Unit Current Metering (NLU5000)

Range Full scale Resolution Accuracy
10% 500A 0.1A ±0.5%rdg+5d
50% 2500A 1A ±0.5%rdg+5d
100% 5000A 1A ±0.5%rdg+5d
200% 10kA 10A ±1.5%rdg+5d

Secondary Injection Output

Output Range Continuous current Intermittent (5min) Intermittent (1min)
0-5V 33A 67A 100A
0-16V 10A 20A 30A

Secondary Injection Metering

Metering range Resolution Accuracy Current trip
10A 0.01A ±0.5%rdg+5d 10.5A
20A 0.01A ±0.5%rdg+5d 21A
100A 0.1A ±0.5%rdg+5d 100A

Timer resolution: 1ms
Timer full scale: 999.999s
Timer accuracy: ±0.01%rdg+2d (4d current mode)
Contact O/C voltage: 24V
Contact S/C current: 20mA
VDC input range: 24-240V DC
Supply: 230V, 45-65Hz, 1ph, 11.5kVA max (23kVA overload for 2 seconds)
Compliance: BS EN61010
Storage temperature: -20°C to 60°C
Operating temperature: 0°C to 45°C
Dimensions (PCU1-SP only): 450 x 275 x 305mm
Weight (PCU1-SP only): 26kg

Recommended Accessories: T&R PCU1-SP Primary Current Injection Test System

Submit Review

Please complete the information below and it will be displayed on our website once it has been reviewed by a member of staff.

Contribution type:

Rating:

Spambot:

Name:

Email: (Not displayed)

Review Title:

Review / Comment Details:



test-meter.co.uk - Home | Your Order | Latest Special Offers | Terms & Conditions | Contact Us | Request Link | Links | Site Map

Prices exclude delivery carriage at £10 and VAT at 20%

All brand names are trade marked to their respective owners.

Company Number: 5394680 VAT Number: GB 842 7016 40


test-meter.co.uk
is a trading name of PAT Training Services Limited.
PAT Training Services Limited.
1 Aston Court,
Town End Close,
LEEDS,
LS13 2AF
UK

Tel: 0113 248 9966
Fax: 0113 248 4276

admin@test-meter.co.uk

Copyright © PAT Training Services Limited, All rights reserved. E&OE