Relay Testing

Products in: High Voltage Test Equipment/Relay Testing/  T&R DVS3 mk2 3 Phase Relay Test Set

 T&R DVS3 mk2 3 Phase Relay Test Set

T&R DVS3 mk2 3 Phase Relay Test Set
Now £8059.00
Was £8726.00
Save £667.00
Buy Now
Ideally suited to testing G59 systems

Be the first to review this product!

Product Features: T&R DVS3 mk2 3 Phase Relay Test Set

T&R DVS3 mk2 3 Phase Relay Test Set

 3 Phase Voltage output from Single Phase supply
 0-133V Ø - N output voltage
0 -266V/292V Ø - N with optional VT box
45VA/phase maximum output
Variable Frequency 40-999.9Hz
Phase shift ±180.0°
Multi-function timing system
Ideally suited to testing G59 schemes
Step change of phase and df/dt
Large back-lit liquid crystal display
Compact and lightweight
Automatic mains voltage selection

The T and R DVS3 mk2 is the new smaller, lighter, higher power version of the T&R DVS3, offering three times the output power of the original DVS3. The exceptionally easy to understand user interface of the DVS3 is retained, allowing simple testing of complex voltage and loss of mains protection systems. Equally at home in a commissioning, maintenance, or laboratory environment, the DVS3 mk2 is a truly flexible system. The DVS3 mk2 has been designed using the latest digital technology to generate a highly stable and accurate output with very low distortion. Each phase output is individually adjustable for voltage and phase angle. In addition, full control of frequency is available. Step changes of any  quantity may be generated with automatic timing of the response of the relay under test. The unit is controlled by a simple user interface with context sensitive menus. Values may be either typed in at the keypad or smoothly varied using a digital potentiometer. The T and R DVS3 mk2 Test system is ideally suited to testing G59 protection, including loss of mains protection. Vector surge and df/dt (ROCOF) relays may be simply tested and timed, as can other protection requiring one to three voltages, including:

  Under and over frequency relays
  Under and over voltage relays
  Synchronising relays
  df/dt & ROCOF relays
  Vector surge relays
  Transducers

T and r Test Equipment DVS3 Display
The display on the DVS3 is back-lit and exceptionally clear. Menu options on the left are selected by dedicated buttons on the panel next to the display, allowing immediate access to adjust voltage, phase and frequency.
Phase to phase and phase to neutral voltages are both shown on the display, along with frequency and phase

In conjuction with a current source (such as the 200ADM), the T and R DVS3 mk2 can be used to test protection requiring current injection with a phase-shiftable voltage including:
  Directional relays
  Distance protection

The display on the DVS3 is back-lit and exceptionally clear. Menu options on the left are selected by dedicated buttons on the panel next to the display, allowing immediate access to adjust voltage, phase and frequency.
Phase to phase and phase to neutral voltages are both shown on the display, along with frequency and phase.
Optional 260V VT box
Power transducers

Supplied Accessories: T&R DVS3 mk2 3 Phase Relay Test Set

Output lead set, (includes:1 x 3m 4 core output lead terminated in 4mm plugs, 1 x 3m 2 core timer lead terminated in 4mm plugs) lead set case, mains lead, spare fuse set and operating manual.

Optional Accessories
Printer,

t and r test equipment VT box
133:266V step up VT box,
133:292V step up VT box.

Product Specifications: T&R DVS3 mk2 3 Phase Relay Test Set

Output
The output of the T&R DVS3 mk2 has four 4mm safety sockets for phases A, B, and C and neutral. The neutral connection may be omitted for a delta connection.
Voltage                                         0-133Vac phase-neutral
                                                       0-230Vac phase-phase
Current (continuous)                200mA at 133V, 120mA at 0.1V*
Current (5min on/ 15min off)  335mA at 133V, 200mA at 0.1V*
Voltage resolution                   0.1V phase-neutral
Phase rotation                          ±180º
Voltage accuracy                    ±0.3%rdg+3d
*The current trip drops linearly between maximum and minimum output voltage. All output ratings are based on an ambient temperature of 25°C.

Timing System

The timing system on the T and R  Test equipment DVS3 mk2 is flexible and transparent in operation. Step changes of any quantity may be generated by typing in value using the keypad. Entering a value in this way automatically resets and starts the timer when the change is applied. The timer then stops on a change of state of either contact input. More complex timing functions are handled by the PF-F-PF mode. Two contact inputs are provided, both of which have LEDs and a mimic on the display to show the contact state. The contact inputs auto-select for normally open or normally closed contacts. A DC voltage can also be used to trigger the timer using the Vdc contact.
Timer resolution             1ms
Timer full scale               999.999s
Timer accuracy              ±0.01%rdg+2d
Contact O/C voltage       24V
Contact S/C current      20mA
Vdc input range             24-240Vdc

Protection and Safety
The DVS3 mk2 Relay  Test System is CE marked and is designed to meet the requirements of BS EN61010. The outputs are protected by overcurrent and thermal trips, and the contact inputs are protected by PTC thermistors. The phase lock current input is fuse protected, and the voltage input is impedance protected. An earth terminal is provided for connection to a local earth.

Supply Requirements

115V/230V±10%±10% auto-selecting, 45-65Hz 1ph 425VA max

Temperature Range

Storage -20°C to 60°C Operating 0°C to 45°C

Lead Set Specifications
1 x 3m 4 core output lead terminated in 4mm plugs
1 x 3m 2 core timer lead terminated in 4mm plugs

Dimensions  and weight
380mm x 314mm x 221mm     9.1kg

Modes of Operation

Variable Frequency Mode
This mode allows full control of frequency, voltage and phase.The voltage and phase may be controlled individually for each phase or for all three phases together. All parameters are continuously variable using the adjust control, and step changes of any value may be generated by typing the required value on the keypad. The new value is applied to the output when the enter key is pressed. The timer automatically resets and starts when a step change of value is entered, and stops if either contact input changes state. Step changes of phase for testing Vector Surge relays are easily generated in this mode.
Frequency resolution     0.01Hz       40.00-99.99Hz
                                             0.1Hz         100.0-999.9Hz
Frequency accuracy      ±0.01%rdg+1d
Phase resolution            0.1º
Phase accuracy             ±0.3º phase to phase

Phase Lock Mode
The frequency and phase of the output are controlled by an external reference in phase lock mode. The reference may be the mains supply to the DVS3 mk2, an external voltage, or an external current. This mode allows testing of directional and distance protection in conjunction with an external current source.
Phase lock range          45-65Hz
External voltage ref.     20-250V AC
External current ref.     0.2-5A AC
Phase resolution          0.1º
Phase accuracy           ±0.3º phase to phase
                                          ±3.0º reference to output

df/dt and ROCOF (Rate Of Change Of Frequency)
Loss of mains protection often takes the form of a df/dt relay, sensitive to the rate of change of frequency over time. The DVS3 MK2 is able to generate a swept frequency output with accurate rates of change of frequency between preset frequencies. The rate of change may be continuously varied to
find the relay setting or stepped to time the relay. The output may be set to either sweep continuously or generate single sweeps with timing.
Frequency range          45.00-65.00Hz
Default sweep range   49.75-50.25Hz (50Hz supply)
                                          59.75-60.25Hz (60Hz supply)
Rate of change range  0.010-3.000Hz/s

Pre-fault - Fault - Post-fault Mode
PF-F-PF mode allows extra flexibility in testing where complex events must be timed or several sets of values must be applied to a relay in turn. This mode allows three sets of values to be set in advance (pre-fault, fault, and post-fault values). The DVS3 MK2 may be set to switch from one state to the next on a change of contact or after a specific time. In addition, the timer may be set to start or stop on any one of the state changes of a change of contact state. This mode allows frequency, phase and voltage
to be changed simultaneously if required.

Recommended Accessories: T&R DVS3 mk2 3 Phase Relay Test Set

Submit Review

Please complete the information below and it will be displayed on our website once it has been reviewed by a member of staff.

Contribution type:

Rating:

Spambot:

Name:

Email: (Not displayed)

Review Title:

Review / Comment Details:



test-meter.co.uk - Home | Your Order | Latest Special Offers | Terms & Conditions | Contact Us | Request Link | Links | Site Map

Prices exclude delivery carriage at £10 and VAT at 20%

All brand names are trade marked to their respective owners.

Company Number: 5394680 VAT Number: GB 842 7016 40


test-meter.co.uk
is a trading name of PAT Training Services Limited.
PAT Training Services Limited.
1 Aston Court,
Town End Close,
LEEDS,
LS13 2AF
UK

Tel: 0113 248 9966
Fax: 0113 248 4276

admin@test-meter.co.uk

Copyright © PAT Training Services Limited, All rights reserved. E&OE