200 Amp Current Injection Test Set T and R Test Equipment 200 ADM-P

Be the first to review this product!

Product Features: T&R 200ADM-P Current Injection Test Set

T&R 200ADM-P Current Injection Test Set

The T&R 200ADM-P is the most recent addition to the range, and provides commissioning and maintenance engineers with a flexible system for testing protective systems. It has an easy to understand panel layout and a simple user interface. The status of every function can be seen at a glance, and there are no complex menus to navigate.

The unit has a range of outputs allowing injection of currents as low as 1mA and as high as 200A. Voltages- up to 240V are available on the main outputs, allowing high impedance current relays and voltage relays to be tested. Four true RMS metering ranges are provided, allowing the full scale of the meter and trip level to be set independently of the selected output-. Industry standard safety connectors are used on all inputs and outputs for convenience, reliability and safety.

The T&R 200ADM-P is comprehensively protected by overcurrent, duty cycle and thermal trips, and keeps the user fully informed of any trip condition.

The back-lit display on the T&R 200ADM-P is bright and clear with a wide viewing angle. The results of a test can be seen here as they appear on the display.

An auxiliary metering input is provided and can measure AC and DC voltage, current, frequency, and the phase between the main current output and an external voltage or current. A stabilised DC supply is provided to power the relay under test, along with an independently variable AC output.

The timing system is very flexible without compro-mising ease of use, allowing trip times, reset times and reclose times to be quickly measured to a high degree of accuracy.

The T&R 200ADM-P can be used to test many types of single phase secondary protection including:

  • Over and under current relays
  • IDMT relays
  • Over and under voltage relays
  • Auto-reclosers
  • Time delay relays
  • Differential relays
  • Earth fault relays
  • Miniature circuit breakers
  • Power relays
  • Tripping relays
  • Thermal relays
 

 

Supplied Accessories: T&R 200ADM-P Current Injection Test Set

The T and R 200ADM-P is supplied with:
Output Lead Set which includes:
2 x 5m 25mm2 200A leads terminated in M10 ring crimps
2 x 5m 2.5mm2 25A leads terminated in 4mm plugs
1 x 5m 2 core auxiliary leads terminated in 4mm plugs
Plastic carrying case for test leads
Operating manual
Mains lead
Spare fuses

Click to go to the top of the page.

Product Specifications: T&R 200ADM-P Current Injection Test Set
  • Clear and simple user interface
  • 0-200A output current
  • True RMS digital metering with memory ammeter
  • Multi-function timing system
  • Auxiliary DC output
  • Variable auxiliary AC output
  • Auxiliary metering input
  • Large back-lit liquid crystal display
  • Thermal and over-current protection
  • Compact and portable
  • Automatic mains voltage selection
  • Optional ADMlog PCdata capture software

    Main Output
    The main output on the unit has four taps, allowing the selection of output voltages up to 240V and output currents up to 200A.

    Range    Continuous    5 minutes   1 minute           6 sec.

    10V            25A               50A                 100A               200A*
    35V           10A                20A                  30A
    100V         3A                    5A                 10A
    240V          1A                   2A                  3A
    240V DC  1A                    2A                  3A
    The above intermittent on times must be followed by an off time of 15 minutes, and are based on an ambient temperature of 25°C.
    *6 second intermittent ratings available with 230V supply

    Auxiliary AC and DC Outputs
    A switched, isolated auxiliary DC supply is available to power the relay under test. The output is protected by a fuse and
    electronic trip circuit.
    DC stabilised output 24V 1.04A
    48V 0.52A
    60V 0.42A
    110V 0.23A
    220V 0.11A

    Variable AC output 0-130Vac 300mA
    The variable AC output is isolated, switched, and fuse protected.

    Metering
    The output is metered by a digital true RMS system with a memory ammeter - whenever the timer stops and the output is
    switched off, the current reading is held on the display.

    Range Resolution Trip current Accuracy
    5.000A 0.001A 5.5A ±0.5%rdg+5d
    20.00A 0.01A 22A ±0.5%rdg+5d
    50.00A 0.01A 55A ±0.5%rdg+5d
    200.0A 0.1A 220A ±0.5%rdg+5d
    A current trip is automatically set to 110% of full scale of the
    selected metering range to protect the device under test.

    Auxiliary Metering Inputs
    An auxiliary metering input is provided which is able to measure RMS and DC voltage or current. In addition the frequency of the
    external input may be measured, and the phase measured between the main output current and the auxiliary metering input.

    Setting Range Resolution Accuracy
    Volts (DC) 270.0V 0.1V ±0.7%rdg+5d
    Volts (AC) 270.0V 0.1V ±0.7%rdg+5d
    Amps (DC) 5.000A 1mA ±0.7%rdg+5d
    Amps (AC) 5.000A 1mA ±0.7%rdg+5d
    Phase 0.1° ±3°
    Frequency 20-100Hz 0.1Hz ±0.2%rdg+1d
    The current input is protected by a F6.3A fuse.

    Timing System
    Range 0-999.999s
    Resolution 1ms
    Accuracy 0.1%rdg+2d (+4d current operated mode)
    The contact circuit has an open circuit voltage of 24Vdc and a short circuit current of 10mA. Each contact circuit will autoselect for normally open or normally closed contacts. A DC voltage of 24-240Vdc may also be used to trigger either timer channel. The output is automatically switched off at the end of the test to safeguard the relay under test.

    The following functions are provided:
    Mode Timer Start Timer Stop
    Internal start Press ‘ON’ Contact 1 or 2
    Single contact Contact 1 Contact 1
    Dual contact Contact 1 Contact 2
    Current operated Current > 10% Current < 10%
    of range of range
    Pulse mode is used for setting the current level in devices sensitive to heating, and allows current to be injected for 400ms and the current recorded.

    RS232
    An RS232 port is provided to allow connection of a printer.

    Protection and Safety
    The unit is protected by electronic over current, duty cycle trips and thermal monitoring on the outputs and fuses on the input
    and regulator. The auxiliary AC output is fuse protected, and the stabilised DC output is protected by an electronic trip and fuse.
    An earth terminal is provided for connection to a local earth. The unit is designed to comply with BSEN61010, and is CE marked.

    Supply Requirements

    115V±10% 50/60Hz 1ph 2300VA max
    230V±10% 50/60Hz 1ph 2300VA max
    The correct range is automatically selected by the unit

    Click to go to the top of the page.
Recommended Accessories: T&R 200ADM-P Current Injection Test Set

test-meter.co.uk - Home | Your Order | Latest Special Offers | Terms & Conditions | Contact Us | Request Link | Links | Site Map

Prices exclude delivery carriage at £10 and VAT at 17.5%

All brand names are trade marked to their respective owners.

Company Number: 5394680 VAT Number: GB 842 7016 40


test-meter.co.uk
is a trading name of PAT Training Services Limited.
PAT Training Services Limited.
Glendale's House,
607 York Road,
LEEDS,
LS9 6NW
UK

Tel: 0113 248 9966
Fax: 0113 248 4276

admin@test-meter.co.uk

Copyright © PAT Training Services Limited, All rights reserved. E&OE