The Seaward Europa Plus can test both 230V & 110V appliances. It can carry out a full range of tests from an Earth bond test to a polarity test. The Europa is the standard tester used by professional Pat testing companies. It is also suitable for in house testing at schools, offices, colleges, hospitals offices, shops & factories. The Europa is perfecly safe for testing PC's, IT equipment and all other office equipment with its safe low current tests.
The Seaward Europa PAT tester also records the asset details you imput along with test results allowing for future download to a PC or printer using optional dedicated software. Up to 5000 Results can be stored in the testers memory, meaning a full days testing can be carried out without any need for interuption to clear the Europa's memory. Like the other PAT testers in the Seaward range it’s portable and comes with a dedicated carry case so you can just pick it up and move on to the next test with ease.
With a Qwerty keyboard to speed up data input, excellent display and on screen guidance for the novice user, the Europa Plus could not be simpler to use. Professional PAT Testers can turn off the on screen help for speedier, hassle free testing.
Supplied Accessories: Seaward Europa Plus PAT Tester
Seaward Europa + PAT Tester includes:
► Luxury carry case with zipped pouches
► Red Protective holster
► Earth bond continuity test lead with crocodile clip
► RS232 download lead
► Adaptor for testing 110V tools and appliances
► Instruction manual
► 12 months manufacturers warranty
► 500 Pass Labels FREE ► 200 Fail Labels FREE
Product Specifications: Seaward Europa Plus PAT Tester
Earth Continuity ► Test Currents 25A AC, 10A AC, 4A AC+-200mA DC
► Display Range 0.01ohms - 19.99ohms
► Pass Value User Defined
► Measurement Technique 4 Wire Measurement, Floating Earth
Earth Screen Continuity
► Test Current 100mA
► Display Range 0.00ohms - 19.99ohms
► Pass Value User Defined
► Measurement Technique 4 Wire Measurement, Floating Earth
Insulation Resistance
► Test Voltage 250V, 500V DC
► Display Range 0.1Mohm - 100Mohm
► Pass Value User Defined
Protective Conductor Current
► Test Voltage 230V
► Display Range 0.1mA - 10mA
► Pass Value User Defined
Touch Current
► Test Voltage 230V
► Display Range 0.1mA - 2.0mA
► Pass Value User Defined
Substitute Leakage
► Test Voltage 40V AC Nominal
► Display Range 1.00mA - 19.99mA
► Pass Value User Defined
Load Test
► Display Range 0kVA - 4.2kVA
► IEC Lead Polarity
► Tests Performed Live/Neutral Continuity and Polarity
If you require a more detailed specification please see the Seaward Europa Plus PDF:
Recommended Accessories: Seaward Europa Plus PAT Tester