| Product Features: Seaward Primetest 350 PAT Tester |

Seaward Primetest 350 PAT Tester
The Seaward Primetest 350 PAT tester can speed up your working day. With the primetest 350 being battery powered there is no need to plug this PAT tester into the mains supply to do PAT tests. It is lightweight and portable, so no lugging heavy PAT Testers around from appliance to appliance. With it's built in Bluetooth technology. downloading PAT test results to your computer is a breeze with no cables to connect. It also encorporates in-situ,high powered, rechargeable batteries. Used in conjunction with the Seaward Bluetooth Scanner (see accessories below) to read bar code labels PAT Testing is significantly speeded up.
This PAT Tester does every test you need to meet the IET Code of Practice revisions, it measures only 26 x 10cm and weights in at under 1kg.
The Prime Test 350 can be set to Novice or Expert mode, with on screen help available for the novice user. The Seaward Primetest 350 has predefined automatic test sequences for all popular types of appliances but users can customise these test settings if desired.
The Seaward Primetest 350 is ideal for testing the electrical safety of UK office electrical appliances items like: computers, monitors, printers, shredders, fax machines, PC's, IT equipment, microwaves, kettles and computer IEC leads.
We also offer a range of Seaward Primetest 350 Kits which can be viewed and purcahsed by clicking here.

|
| Supplied Accessories: Seaward Primetest 350 PAT Tester |
► Seaward Primetest 350 PAT Tester 356A910
► Deluxe carry case with zipped pouches
► Built in rechargeable batteries
► Test Lead with crocodile clip and mains lead
► USB Bluetooth adaptor
► 110V Socket Adaptor
► Instruction manual CD and Reference Guide
► 12 months manufacturers warranty
► FREE 500 Pass Labels
► FREE 200 Fail Labels
► TEST-METER EXCLUSIVE: FREE PAT Testing Frequency & Test Limit Reference Guide
Order your Seaward Prime Test 350 today from www.test-meter.co.uk |
| Product Specifications: Seaward Primetest 350 PAT Tester |
Earth Continuity
► Test Current: +/- 200mA
► Display Range: 0.00ohm - 19.99ohm
► Pass Value: User Defined
Insulation Resistance
► Test Voltage: 500V / 250V DC @ 1mA nominal
► Display Range: 0.01Mohm - 199Mohm
► Pass Value: User Defined
IEC Lead Test
► Tests Performed: Earth, Insulation Resistance, Live & Neutral Continuity
Protective Conductor Current/Load
► Test Voltage: 195V - 230V, 45Hz-60Hz
► Display Ranges: 0.15mA - 19.99mA, 0.00kVA - 4.00kVA, 0.00A - 16.00A
► Pass Value: User Defined
Touch Current/Load
► Test Voltage: 195V - 230V, 45Hz-60Hz
► Display Ranges: 0.07mA - 3.5mA, 0.00kVA - 4.00kVA, 0.00A - 16.00A
► Pass Value: User Defined
Alternative Leakage Current
► Test Voltage: 40V, 50Hz
► Display Range: 0.10mA - 19.99mA
► Pass Value: User Defined
RCD Trip Time
► Test Current: 30mA rms, 0º/180º auto switched
► Display Range: 0ms - 200ms
Loop Impedance
► Test Current: Non-tripping for >30mA RCD
► Display Range: 0.0ohm - 199ohm
Power Socket Test
► Voltage Range: 195V - 253V
► Voltage Indicators: phase-Earth & phase-neutral
► Memory: 8000 records
► Weight: 0.9kg
► Dimensions: 260mm x 100mm x 80mm
► Power Source: 6 x AA Batteries
|
| Recommended Accessories: Seaward Primetest 350 PAT Tester |
|
Reviews / Comments
"Good Afternoon
I would just like to send this e-mail to say thanks for the service we recently received from your company. We have previously ordered supplies from yourselves and we have always been dealt with in a friendly and hassle-free manner, including our recent order to update our equipment from a Seaward Supernova to a Primetest350.
I phoned initially to get some information in regards to the 17th edition regulations and any changes to equipment. Your guys gave me all the info I needed and discussed our current equipment and testing structure. It was then mentioned that the Supernova that we purchased at the beginning (advise given from a different company) wasn’t the best option as 90% of our hardware is IT equipment. With the information and advice given we mulled it over and decided to upgrade.
I have just completed an office test using the Primetest and it makes the job twice as easy to complete, not to mention a lot less hassle with the portability of the unit. I know people are quick enough to complain if there is a problem but not always willing to let you know when you have done well.
So a big thank you to all the chaps that gave us the advice and also to Lasse Tonnesen for dealing with the order of the new bits and buyback of our old gear in a very quick and professional manner. Excellent service from start to finish.
Many Thanks"
Feb 17 2009, 09:28 AMby John Attwell