Product Features: Kewtech KT76 PAT Tester

PAT Testing Pass and Fail Labels

Kewtech KT76 PAT Tester

 

The Kewtech KT76 PAT Tester is the latest portable appliance tester in the range from Kewtech. The KT76 is a simple to use dual voltage, manual PAT tester suitable for use on Class 1 and Class 2 appliances including both 230V domestic and 110V industrial appliances.

Kewtech KT76 testing features
Tests both 230V & 110V appliances
200mA Continuity test
250V & 500V Insulation test
Earth, substitute & touch leakage tests
Extension & IEC lead testing
Calibrated earth bond lead
Adjustable pass and fail limits

The large screen displays all the relevant test data with numerical values and visual indication of whether the asset has passed or failed the test. Below the screen are test buttons allowing straightforward selection of earth, insulation, IEC lead polarity and leakage tests. The Kewtech KT 76 tester enables full compliance with the latest edition of the IEE Code of Practice, including 250V and 500V insulation testing, and within the lid a quick PAT testing reference guide is provided which outlines permitted minimum and maximum values. With this information easily to hand, the KT76 has adjustable presets allowing you to select the correct set up to suit your electrical safety testing requirements. The new KT76 appliance tester is stored in a robust moulded case with a rating of IP40, providing a high level of protection with room in the lid for test leads to be stored.

Supplied Accessories: Kewtech KT76 PAT Tester

Kewtech KT76 Portable Appliance Tester
FREE 500 Pass Labels

FREE 200 Fail Labels
IEC mains cord
Test lead
Instruction Manual
Quick reference guide

Product Specifications: Kewtech KT76 PAT Tester

Earth Continuity
Display Range: 0.01 to 19.99 Ω
Measuring Range: 0.05 to 19.99 Ω
Accuracy: ±(5% + 2 digits)
Test current: 200mA minimum
Test voltage: 6V nominal
Insulation
Display Range: 0.01 to 19.99 MΩ
Measuring Range: 0.10 to 19.99 MΩ
Accuracy: ±(5% + 2 digits)
Test current: >1mA <2mA into 2KΩ
Substitute Leakage
Display Range: 0.10mA to 19.99mA
Measuring Range: 0.25mA to 19mA
Accuracy: ±(5% + 2 digits)
Test current: <10mA into 2KΩ
Test voltage: 40V rms 50Hz AC
Earth Leakage Current
Display Range: 0.15mA to 19.99mA
Measuring Range: 0.25mA to 19mA
Accuracy: ± (5% + 2 digits)
Test voltage: Mains voltage 50Hz AC
Touch Leakage Current
Display Range: 0.10mA to 3.5mA
Measuring Range: 0.10mA to 1.99mA
Accuracy: ±(5% + 2 digits)
Test voltage: Mains voltage 50Hz AC
Extension Lead/IEC Lead Test
Earth continuity, insulation resistance as above
Check for Live and Neutral open circuit, short circuit or reversed polarity
Overvoltage Category: CAT II 300V

Recommended Accessories: Kewtech KT76 PAT Tester

Submit Review

Please complete the information below and it will be displayed on our website once it has been reviewed by a member of staff.

Contribution type:

Rating:

Spambot:

Name:

Email: (Not displayed)

Review Title:

Review / Comment Details:



test-meter.co.uk - Home | Your Order | Latest Special Offers | Terms & Conditions | Contact Us | Request Link | Links | Site Map

Prices exclude delivery carriage at £10 and VAT at 20%

All brand names are trade marked to their respective owners.

Company Number: 5394680 VAT Number: GB 842 7016 40


test-meter.co.uk
is a trading name of PAT Training Services Limited.
PAT Training Services Limited.
1 Aston Court,
Town End Close,
LEEDS,
LS13 2AF
UK

Tel: 0113 248 9966
Fax: 0113 248 4276

admin@test-meter.co.uk

Copyright © PAT Training Services Limited, All rights reserved. E&OE