Circuit Test
► Open Circuit Voltage: 15 V a.c. typical
► Short Circuit Current: 100 mA a.c. typical
Insulation Test
► Range: 0 - 50 M½
► Accuracy: 5.0% ± 100 k½ (² 20 M½)
► Compliance: 500 V. d.c. at 0.5 M½
► Pass Band Options: 0.25, 0.3, 0.5, 1, 2, 4, 5, 7, 8, 10, 20, 50 M½
Earth Bond Test
Range:
► 0 m½ - 999 m½ Resolution 1 m½
► 1000 m½ - 1999 m½ Resolution 10 m½
Accuracy:
► 0 m½ <R> 499 m½ 5.0% ±5 m½
► 500 m½ <R> 1999 m½ 5.0% ±50 m½
► Open Circuit Voltage: 10 V a.c. typical
► Test Current: 10 A or 25 A into 0.1 ½ typical
► Pass Band Options: 50, 100, 200, 300, 400, 500, 600, 750, 800 m½, 1.5, 2.0 ½
Earth Continuity Test
Range:
► 0 m½ - 999 m½ Resolution 1 m½
► 1.00 ½ - 9.99 ½ Resolution 10 m½
Accuracy:
► 0 m½ <R> 999 m½ 5.0% ±5 m½
► 1.00 ½ <R> 9.99 ½ 5.0% ±10 m½
► Open Circuit Voltage: 4 V d.c. typical
► Test Current: 200 mA typical constant current (R² 1 ½)
► Pass Band Options: 50, 100, 200, 500, 750 m½, 1.0, 1.5, 2.0, 2.5, 5, 7.5, 10 ½
Operation Test (Energised from 230 V supply)
► Range: 0 - 3.0 kVA
► Accuracy: 0 <VA >99 VA 5.0% ±5 VA 100 <VA >999 VA 5.0% ±10 VA 1.0 <kVA >3.0 kVA 5.0% ±100 VA
► Reference: Reading corrected to 230 V
► Pass Band Options: 50, 100, 200, 350, 500, 700, 1000, 1200, 1500, 2000, 2500, 3000 VA
Operation Test (Energised from 110 V supply)
► Range: 0 - 1.6 kVA (3 kVA short term)
► Accuracy: 0 <VA >99 VA 5.0% ±5 VA 100 <VA >999 VA 5.0% ±10 VA 1.0 <VA >1.6 kVA 5.0% ±100 VA
► Reference: Reading corrected to 110 V
► Pass Band Options: 50, 100, 200, 350, 500, 700, 1000, 1200, 1500, 2000, 2500, 3000 VA
Earth Leakage Test
► Range: 0 - 15 mA
► Accuracy: 5.0% ±100 µA
► Reference: Reading corrected to 253/121 V (As if 10% High Supply)
► Pass Band Options: 0.25, 0.5, 0.75, 1.0, 1.5, 2.0, 3.5, 5.0, 7, 7.5, 10, 15 mA
Fuse Test
► Open Circuit Voltage: 5 V d.c. typical
► Test Current: 500 mA short circuit typical
► Indication: Audible using internal buzzer
Flash Test
► Range: 0 - 3 mA
► Accuracy: 5.0% ±100 µA
► Output Voltage: Class 1 1500 V a.c. (typical)
► Class 2 3000 V a.c. (typical)
► Output Current: < 3.5 mA @ 253/121 V
► Pass Band Options: 0.2, 0.3, 0.4, 0.5, 0.6, 0.75, 1.0, 1.2, 1.5, 2.0, 2.5, 3.0 mA
Extension Lead Test
► Bond test (10 or 25 A)
► Insulation test
► Polarity test indicates: Correct polarity
► Crossed connections L/N
► Short circuit L/N
► Open circuit L/N
On Board Database Specifications
► Clients: 10
► Locations: 20
► Test Groups: 50
► Users: 10
Appliances:
► 1000 with the following data fields; ID, description, group, serial no, room, VA rating, last and next test dates, retest frequency and fuse rating + previous test results
Supply Voltage
► Mains supply: 99 - 121, 207 - 253 V 50 Hz
Communications
► 9 way male ‘D’ RS232 connector:
► Interface to PC and optional Bar Code Scanner
► 25 way female ‘D’ connector:
► Connection to parallel printer
Safety Specifications
► The PAT4 complies with BSEN 61010-1:1990
► Electromagnetic Compatibility
► In accordance with IEC61326 including amendment No.1
Physical Specifications
► Weight (unpackaged inc. std. accessories):
► 6.0 kg (PAT4 DV/3)
► 6.9 kg (PAT4 DVF/3)
► Width (Including Handle and Lid): 375 mm
► Depth: 330 mm
► Height: 200 mm