Kane 452NO Flue Gas Analyser

SKU: KANE452NO
  • Measures CO2, CO, temperature, pressure and NO (0 to 100ppm)
  • Structured commissioning test for boilers and dual-pump protection system for CO
  • Calculates a range of factors including O2 level, excess air, CO/CO2 ratio & efficiency
More Info
Discontinued

Kane 452NO Flue Gas Analyser

This product has been discontinued - please call us on 0113 2489966 for a suitable alternative.

The Kane 452NO Flue Gas Analyser measures CO levels (0 to 2000ppm), NO (0 to 100ppm), differential temperature, and differential pressure (±80mbar) and can even directly measure CO2 from 0 to 20% via an infrared sensor. This enables calculation of O2 level, excess air, CO/CO2 ratio and combustion efficiency. Additionally, one of the most impressive features of the analyser is the NO measurement from 0 to 100ppm.

Carbon monoxide measurement is aided by a dual pump system that provides over-range protection and there is even a structured commissioning test which carries out the testing of new boilers in accordance with Technical Bulletin 143. The Kane 452NO is compatible with systems burning a wide range of different fuels.

The analyser has various applications including installation and servicing of appliances, performing safety checks, measuring ambient CO build up, let by & tightness testing, assessing combustion performance and flue draught measurements.

The Kane 452NO has a six-line LCD display with a data hold function that can freeze results on screen. Additionally, readings are saved to the analyser’s large internal memory and can be recalled to the screen or printed using an infrared fast printer. The analyser comes supplied with a flue probe, pressure connectors, a charger and calibration report.

Key Features

  • Carbon dioxide range: 0 to 20%
  • Carbon monoxide range: 0 to 2000ppm
  • Nitric oxide range: 0 to 100ppm
  • Differential temperature range: 0 to 600˚C
  • Differential pressure range: ±80mbar
  • Oxygen level calculation
  • Excess air calculation
  • CO/CO2 ratio calculation
  • Combustion efficiency calculation
  • Dual pump CO over-range protection system
  • Structured TB143 commissioning test
  • Large internal memory
  • Six-line digital display
  Kane 452NO Standalone Kane 452NO Kit Kane 452NO Oil Kit
Kane 452NO Flue Gas Analyser
Flue probe
Pressure connectors
Charger
Calibration report
Kane IRP-2 Infrared Printer  
Kane rucksack  
Kane MSP Smoke Pump    
Kane oil pressure kit    

What's In The Box?

  • Kane 452NO Flue Gas Analyser
  • Probe
  • Pressure connectors
  • Charger
  • Quick guide reference
  • Calibration report
Specification
  • CO Range: 0 to 2000 ppm
  • Differential Pressure: Normal range: ±80 mbar (Maximum over range without damage to sensor is ±400 mbar)

Dimensions

  • Handset: 200 x 90 x 45mm
  • Probe: 300 x 6mm dia. with 240mm long stainless steel shaft and Type K thermocouple 

Flue Temperature

  • Range: 0 to 600°C
  • Resolution: 0.1°C
  • Accuracy: +2°C or +0.3% reading

Gas Measurements

  • Oxygen range: 0 to 21%
  • Oxygen resolution: 0.1°C
  • Oxygen accuracy: +0.3%
  • Carbon monoxide range: 0 to 2000 ppm
  • Carbon monoxide resolution: 1 ppm
  • Carbon monoxide accuracy: +3 ppm or ±5% reading
  • Nitric oxide range: 0 to 100 ppm
  • Nitric oxide resolution: 1 ppm
  • Nitric oxide accuracy: +2 ppm at 100 ppm
  • Hose Length: 3 m
  • Inlet Temp Internal Sensor: 0 to 50°C
  • Resolution: 0.1°C
  • Accuracy: +1.0°C or +0.3% reading
  • Fuels: Natural Gas, Butane, Propane, LPG, 28 sec oil, 35 sec oil, Wood pellets
  • Weight 0.8 kg