Kane 905 Commercial Flue Gas Analyser

SKU: KANE905
  • Measures temperature, pressure, oxygen and carbon monoxide in flues
  • Upgradeable design allows user to add two measurement sensors
  • Suitable for commercial boilers running from gas, oil or biomass
More Info
Discontinued

Kane 905 Commercial Flue Gas Analyser

This product has now been discontinued. The closet replacement product is the Kane 975 Industrial Flue Gas Analyser. For alternative products please feel free to call the office to discuss your requirements.

The Kane 905 Commercial Flue Gas Analyser is an ideal instrument for engineers working on installing, commissioning and maintaining commercial appliances running from a variety of oils, gases and biomass fuels. As standard, it is capable of measuring oxygen (0 to 25%), CO (0 to 4000ppm), differential pressure, and inlet/flue gas/differential temperature. Additionally, there are calculation options that can produce values for CO2, CO/CO2 ratio, excess air, and combustion efficiency.

Further measurement sensors are available as additional options thanks to the analyser’s upgradeable design. The Kane 905 has options for enhanced CO (0 to 100,000ppm), NO (0 to 100ppm; 0 to 5000ppm), O2 (0 to 1000ppm), and SO2 (0 to 100ppm; 0 to 5000ppm). NOx values can be calculated when the appropriate sensor is added. It is also possible to add a wireless Android module that enables data transfer over KANE LIVE software and the free Kane printer app. Please note that each Kane 905 can be fitted with a maximum of TWO additional sensors.

Up to eight readings can be shown simultaneously on the Kane 905’s four-line digital display and it is operated via a simple push button interface The analyser has a large internal memory that can store up to 150 test results and it is capable of communicating wirelessly with an optional IR printer to create hard copies on site.

The Kane 905 comes supplied with a flue probe, a charger, carry case and a calibration report. It has a battery life of over 8 hours and has a portable lightweight design despite its heavy duty applications.

Key Features

  • Measurement: O2, CO, pressure, temperature
  • Calculation: CO2, CO/CO2, excess air, efficiency
  • Optional measurement: High CO, SO, NO, O2
  • Optional calculation: NOx
  • Suitable for oils, gases and biomass
  • Multiple readings on digital screen
  • 150-reading internal memory
  • 8-hour battery life

What's In The Box?

  • Kane 905 Flue Gas Analyser
  • Flue probe
  • Battery charger
  • Kane 905 instruction manual
  • Calibration report
  • Carry case
Specification

Temperature Measurement

  • Flue temperature range: 0 to 1200˚C
  • Flue temperature accuracy: ±2˚C ± 0.3%
  • Flue temperature resolution: 0.1˚C/˚F
  • Inlet temperature range: 0 to 50˚C
  • Inlet temperature accuracy: ±1˚C ± 0.3%
  • Inlet temperature resolution: 0.1˚C/˚F

Gas Measurements

  • Oxygen range: 0 to 25%
  • Oxygen accuracy: ±0.2%
  • Oxygen resolution: 0.1%
  • Carbon monoxide (H2 compensated) range: 0 to 4000ppm
  • Carbon monoxide (H2 compensated) accuracy: ±5ppm <100ppm; ±20ppm <400ppm; ±5% <400ppm
  • Carbon monoxide (H2 compensated) resolution: 1ppm

Pressure Measurement

  • Pressure range: 150mbar
  • Pressure accuracy: ±5%
  • Pressure resolution: 0.1mbar

Calculated Values

  • Carbon dioxide range: 0 to 99.9%
  • Carbon dioxide accuracy: ±0.3%
  • Carbon dioxide resolution: 0.1%
  • Losses range: 0 to 99.9%
  • Losses accuracy: ±1%
  • Losses resolution: 0.1%
  • Efficiency range: 0 to 99.9%
  • Efficiency accuracy: ±1%
  • Efficiency resolution: 0.1%
  • Excess air range: 0 to 2885%
  • Excess air accuracy: ±0.2%
  • Excess air resolution: 0.1%
  • (Nett) temperature range: 0 to 1200˚C
  • (Nett) temperature accuracy: ±2˚C ± 0.3%
  • (Nett) temperature resolution: 1˚C
  • CO/CO2 ratio range: 0 to 0.9999
  • CO/CO2 ratio accuracy: ±0.0001
  • CO/CO2 ratio resolution: 0.0001
  • Poison index range: 0 to 99.99 range
  • Poison index accuracy: ±0.01
  • Poison index resolution: 0.01

Optional Gas Measurements

  • Carbon monoxide (high range) range: 0 to 100,000ppm
  • Carbon monoxide (high range): ±5ppm <100ppm; ±20ppm <400ppm; ±5% <400ppm
  • Carbon monoxide (high range) resolution: 1ppm
  • Nitric oxide (low) range: 0 to 100ppm
  • Nitric oxide (low) accuracy: ±3ppm <200ppm; ±5ppm <100ppm
  • Nitric oxide (low) resolution: 1ppm
  • Nitric oxide range: 0 to 5000ppm
  • Nitric oxide accuracy: ±5ppm <100ppm; ±5% >100ppm
  • Nitric oxide resolution: 1ppm
  • Nitrogen dioxide range: 0 to 100ppm
  • Nitrogen dioxide accuracy: ±3ppm <200ppm; ±5ppm <100ppm
  • Nitrogen dioxide resolution: 1ppm
  • Sulphur dioxide range: 0 to 5000ppm
  • Sulphur dioxide accuracy: ±5ppm <100ppm; ±5% >100ppm
  • Sulphur dioxide resolution: 1ppm

General

  • Pre-programmed fuels: Natural gas, Town gas, Gascor, Light Oil, Heavy Oil, Propane, Butane, Anthracite, Coke, Coal, Kinsale Gas
  • Dimensions (handset): 220mm x 55mm x 120mm
  • Dimensions (probe): 240mm x ø8mm x 285mm, 1.5m neoprene hose
  • Operating temperature: -5˚C to +50˚C/10% to 90% RH non condensing
  • Power supply: Input, 110Vac/220 Vac nominal; Output, 12 Vac off load
  • Battery life: >8 hours