Martindale EZ2500 E-Ze Test Loop Tester

SKU
MARTEZ2500
Patented T-Safe Technology provides fast and accurate measurement without tripping 30mA, or higher, RCDs. Just plug it in and note the readings!
More Info
inc VAT £142.80 ex VAT £119.00
Contact for lead time
 

Product Details

Martindale EZ2500 Loop Tester

The Martindale EZ2500 has measures PSCC (prospective Short Circuit Current), phase-neutral loop impedance and PFC (Prospective Fault Current) and comes supplied with a mains lead. An optional Martindale TL88 Flying Test lead set  is available for use at distribution boards, junction boxes and lighting circuits. The display cycles through all the test results, ending up with a convenient summary display showing all the key measurements (P-E, P-N, PSCC and PFC) together.

Patented T-Safe™ Technology provides fast and accurate measurement without tripping 30mA RCDs. Just plug it in and note down the readings!

The Martindale EZ2500 scrolls through in sequence on the clear, back-lit, 32 character display to show socket problems or high/ low voltage conditions. The loop impedance test results, PFC and PSC calculations are then displayed. Complies with BS EN 61010, BS EN 61557 & BS 7671 (17th Edition). Designed for use with 30mA and greater RCDs.

Martindale EZ2500 Key Features:

  • Operating voltage: 230V AC
  • Earth loop accuracy: ±(3% + 0.1Ω +2 digits).
  • Non trip loop tests: P-E & P-N
  • Loop impedance ranges: 0.1 to 3kΩ.
  • PFC and PSC test
  • Clear Back-lit display
  • Socket test
  • Voltage test
  • Overvoltage: 300V CAT III
  • Dimensions: 140 x 80 x 55
  • Weight: 230g
What's In The Box?
  • Martindale EZ2500 Loop Tester
  • Zip carry case
  • Mains Lead
  • Instructions
More Information
Specification
  • Nominal Voltage Rating: 220 - 240 V
  • Voltage Range for Wiring Error Detection: 30 - 275 V
  • Open Loop indication: If Open PE or PN Loop is detected,no Impedance test takes place.
  • Voltage Range for Impedance Measurement: 198 - 264 V
  • Frequency: 50 Hz
  • Loop Impedance Ranges: 0-8.99Ω, 9.0-89.9Ω,90-899Ω,900-1699Ω,1700-3000Ω

Phase Earth Loop Impedance Accuracy:

  • 0 - 8.99Ω, ± 4% ± 0.05Ω
  • 9.0 - 89.9Ω, ± 5% ± 0.5Ω
  • 90 - 899Ω, ± 5% ± 5Ω
  • 900 - 1699Ω ± 5% ± 30Ω
  • 1700 - 3000Ω indicative

Phase Neutral Loop Impedance Accuracy:

  • 0 - 8.99Ω, ± 4% ± 0.05Ω
  • 9.0 - 89.9Ω, ± 5% ± 0.5Ω
  • 90 - 899Ω, ± 5% ± 5Ω
  • 900 - 1699Ω ± 5% ± 30Ω
  • Voltage Accuracy: ± 4 % Frequency Accuracy: ± 4 %
  • Temperature Range: -10° to 40° C at max 80 % Relative Humidity (Non-Condensing)
  • Power consumption: < 1.6 W
  • Overvoltage category: CATIII/300V Pollution degree: 2
  • Supply: mains Dimensions: 145 x 85 x 53mm + Cable
  • Weight: 240g plus cable & case

For a detailed specification please see the Martindale EZ2500 Loop tester PDF pdf

If you would like to see the instruction manual for the Martindale EZ2500 please see this PDF pdf

* Note:- Measurement accuracy can be affected by highly inductive or capacitive components distributed on the supply.