Martindale HPAT400 Kit A

SKU: MARTHPAT400KITA
  • Suitable for testing Class I appliances, Class II appliances and extension leads
  • Comes supplied with a microwave leakage detector and a socket tester
  • PAT register book, PAT certificate pad, and a set of PASS & FAIL labels
More Info
£358.80 £299.00
In Stock - Available Next Day

Martindale HPAT400 Kit A

Martindale HPAT400 Test Kit A is a great option for those conducting appliance testing in offices, residential blocks, and other domestic and commercial environments. It includes a Martindale HPAT400 PAC Checker, PAT labels, testing accessories and record keeping accessories.

The Martindale HPAT400 PAC Checker is capable of performing earth bond testing, insulation resistance testing, polarity checking and leakage current testing. It is suitable for Class I appliances, Class II appliances and power leads although it is not appropriate for longer extension leads.

The Martindale HPAT400 has automatic test sequences for different appliance and lead types; all the user needs to do is connect the PAC checker and then press the appropriate button. A PASS/FAIL indication according to internal limits is provided on the clear digital display.

Various accessories are supplied with Martindale HPAT400 Kit A including PASS labels, FAIL labels, a microwave leakage detector, a socket tester, an extension lead adaptor, a PAT register book and a PAT certificate pad.

Kit Contents

  • Martindale HPAT400 PAC Checker
  • Microwave Leakage Detector
  • 50 Microwave Emission Labels
  • PAT Certificate Pad
  • PAT Register Book w/ Frequency of Inspection
  • IEC Clover Leaf Adaptor
  • Martindale CP501 Socket Tester
  • 1000 Pass Labels
  • 200 Fail Labels
  • 250 PassWrap Cable Labels
  • Earth Bond Test Lead
  • 230V Extension Lead Adaptor
  • Mains Lead
  • 6 x Rechargeable Batteries
  • HPAT400 Carry Case
  Kit A Kit B Kit C Kit D
Martindale HPAT400 PAC Checker
Microwave Leakage Detector    
50 Microwave Emissions Labels    
PAT Certificate Pad    
PAT Register Book w/ Frequency of Inspection
IEC Clover Leaf Adaptor  
Martindale CP501 Check Plug  
1000 Pass Labels
200 Fail Labels
250 PassWrap Cable Labels
250 Tuff Tag Cable Labels    
Earth Bond Test Lead
Mains Lead
230V Extension Lead Adaptor
110V Appliance Adaptor    
110V Extension Lead Adaptor    
Rechargeable Batteries
HPAT400 Carry Case
Portable Appliance Tester Kit Carry Case  

What's In The Box?

  • Martindale HPAT400 PAC Checker
  • Microwave Leakage Detector
  • 50 Microwave Emission Labels
  • PAT Certificate Pad
  • PAT Register Book w/ Frequency of Inspection
  • IEC Clover Leaf Adaptor
  • Martindale CP501 Socket Tester
  • 1000 Pass Labels
  • 200 Fail Labels
  • 250 PassWrap Cable Labels
  • Earth Bond Test Lead
  • 230V Extension Lead Adaptor
  • Mains Lead
  • 6 x Rechargeable Batteries
  • HPAT400 Carry Case
Specification

EARTH CONTINUITY

  • Test voltage: 4V DC (into open circuit) Test current: 200mA DC (into short circuit)
  • Accuracy: ± 0.03Ω
  • Pass limits: Lead ≤ 0.20 Ω = PASS; Class I ≤ 0.20 Ω = PASS

INSULATION

  • Fixed voltage: >500V DC at 1mA (< 625V DC into open circuit)
  • Test current: 1.5mA (into short circuit)
  • Accuracy: ± 0.1MΩ
  • Pass limits: Lead: ≥ 1.0 MΩ; Class I: ≥ 1.0 MΩ; Class II: ≥ 2.0 MΩ

FUSE CHECK

  • Test voltage: 4V DC (into open circuit)
  • Test current: 200mA DC (into short circuit)
  • Pass level: >2mA

GENERAL

  • Overload protection: 300V AC/DC