Megger DET4TCR2 Rechargeable Earth Tester + Pro ET Kit

SKU
MEGGDET4TCR2KIT
  • Megger DET4TCR2 Rechargeable Earth Tester serves as base device
  • Allows attached rod technique and stake-less clamps thanks to ICLAMP and VCLAMP
  • Professional testing kit with 2 x 50m wires, 2 x 30m wires, auger stakes and tape measure
More Info
inc VAT £2,022.00 ex VAT £1,685.00
Typically ships in 5-7 working days
 

Product Details

Megger DET4TCR2 Professional Earth Testing Kit

With the Megger DET4TCR2 Rechargeable Earth Tester as its base device, the Megger DET4TCR2 Professional Earth Testing Kit offers comprehensive ground-testing capacity thanks to the tester’s accuracy and versatility in addition to an array of practical ground-testing paraphernalia. The Megger DET4TCR2 itself performs two-pole, three-pole and four-pole ground testing; measures current leakage; and assesses ground voltage noise. The user has the choice of a range of different outputs for voltage, current and frequency which helps negate interference from voltage noise up to 40V peak to peak and operation is very straightforward, even when wearing gloves.

The Megger DET4TCR2 Earth Tester is weatherproof to IP54 standard and the backlit LCD screen makes readings legible in all lights so it is ideal for ground testing outside. The tester is full rechargeable and even comes with an AC/DC charger as standard.

The extra items provided in the Megger DET4TCR2 Professional Kit supplement the tester by making it more adaptable and by increasing its range. Firstly, the ICLAMP (also supplied in the Megger DET4TCR2 Kit with Clamps) allows attached rod technique testing whereas the VCLAMP allows stake-less measurements when conditions are unsuitable for driving in stakes. A field calibration check is also supplied which helps ensure accurate readings.

Other features of the Megger DET4TCR2 Professional Kit include a standalone ground-testing kit which features two 50m wires, two 30m wires, a tape measure and another hard carry case, in addition to the case that contains the earth tester, clamps and wire-and-stake set that comes with the device as standard. The range of the earth tester is therefore greatly increased and the kit allows the user to perform completely comprehensive earth tests.

Key Features

  • Megger DET4TCR2 Earth Tester
  • Professional ground testing kit including 2 x 50m wires, 2 x 30m wires, four auger stakes, a tape measure and hard carry case
  • Standard hard carry case
  • Standard stake and wire kit (15m, 10m, 10m, 3m)
  • ICLAMP for ART testing
  • VCLAMP for stake-less testing
  • Field calibration check for instrument and clamps
  • Right angle terminal adaptors for connecting bare wires to terminals
  • Calibration certificate
What's In The Box?
  • Megger DET4TCR2 Earth Tester
  • Standard hard carry case
  • Standard stake and wire kit (15m, 10m, 10m, 3m)
  • ICLAMP for ART testing
  • VCLAMP for stake-less testing
  • Field calibration check for instrument and clamps
  • Right angle terminal adaptors for connecting bare wires to terminals
  • Calibration certificate

PLUS professional ground testing kit including:

  • 2 x 50m wires
  • 2 x 30m wires
  • 4 x auger stakes
  • 1 x tape measure
  • 1 x hard carry case
More Information
Specification
  • Ingress protection: IP54
  • C stake, P stake and Noise check: Automatic
  • Noise rejection: 40 V pk to pk
  • 2-wire, 3-wire, 4-wire test: Yes, no shorting links required
  • No disconnect testing (ART): Yes, with ICLAMP
  • Stakeless measurement: Yes, with ICLAMP and VCLAMP

Instrument output

  • Voltage: ±25 V or ±50 V at 94 Hz, 105 Hz, 111 Hz and 128 Hz
  • Current: 4.5 mA or 0.45 mA or 0.045 mA
  • Ground current range with clamp: 0.5 mA to 19.9 A
  • Ground current accuracy: 5% ±3 digits
  • Ground voltage range: 0 to 100 V ac
  • Ground voltage accuracy: 2% ±2 V

Resistance ranges

  • 2, 3, 4 pole: 0.01 Ω to 200 kΩ
  • ART: 0.01 Ω to 200 kΩ
  • Stakeless: 0.01 Ω to 200 Ω

Resistance accuracy

  • 2P measurements: 2% ±3 digits
  • 3P measurements: 2% ±3 digits
  • 4P measurements: 2% ±3 digits
  • ART measurements: 5% ±3 digits
  • Stakeless measurements: 7% ±3 digits

Maximum probe resistance

  • Rp limit: 200 kΩ (50 V output voltage)
  • Rc limit: 200 kΩ (50 V output voltage)
  • Limits reduced to 100 kΩ for 25 V output voltage
  • Limits reduced to 5 kΩ for 0.01 Ω resolution
  • Display: 3.5” digit high contrast liquid crystal, backlit
  • Battery type: DET4TC2: 8 x rechargeable AA cells
  • Operating temperature range: -15 °C to +55 °C / 5 °F to 131 °F
  • Storage temperature range: -40 °C to +70 °C / -40 °F to 158 °F

Safety

  • Complies with the requirements of IEC61010-1 100V CAT IV between terminal pairs.*

EMC

  • In accordance with IEC61326-1

Standards Compliance

  • Complies with the requirements of KEMA K85B
  • Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective measures”.
  • Part 1 - General requirements
  • Part 5 - Resistance to earth
  • Dimensions: 203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in)
  • Weight: 1kg (2.2lb)

*The CAT IV 100 V rating is dependent on the use of a lead set of at least this rating, for example the optional two wire lead set part number 1001-858.