Output The output of the T&R ART3V has four 4mm safety sockets for phases A, B, and C and neutral. The neutral connection may be omitted for a delta connection and the neutrals may be linked for star connection using the provided accessory. - Voltage: 0-450Vac phase-neutral
- Current (continuous): 40mA at 450V
- Voltage Resolution: 0.01V phase-neutral
- Phase Rotation: 360˚ (±180º)
- Voltage Accuracy: ±0.1%rdg+2d
*All output ratings are based on an ambient temperature of 25˚C Timing System The timing system on the T and R Test equipment ART3V is flexible and transparent with different modes of operation. In INTERNAL START mode step changes of any quantity will automatically reset and start the timer when the change is applied. The timer then stops on a change of state of either contact set. Contacts can be used to trigger the timer based on external relay changes. Also, more complex timing functions are handled by the Fault Config mode. Two contact inputs are provided, both of which have LEDs and an icon on the display to show the contact state. The contact inputs auto-select for normally open or normally closed contacts. A DC voltage can also be used to trigger the timer using the Vdc contact. - Timer Resolution: 1ms
- Timer Accuracy: ±0.01%rdg+2d
- Contact O/C Voltage: 24V
- Contact S/C Current: 20mA
- Vdc Input Range: 24-240Vdc
USB Data The ART3V can be connected to a USB keyboard for adding comments to tests. Each test is stored to a USB memory key with each comment. The data is stored in a .CSV format allowing it to be opened in all types of desktop PC spreadsheet software. Protection and Safety The ART3V Relay Test System is CE marked and is designed to meet the requirements of BS EN61010 and EMC tested to BS EN 61326. The outputs are protected by overcurrent and thermal trips, and the contact inputs are protected by PTC thermistors. The phase lock current input is fuse protected, and the voltage input is impedance protected. An earth terminal is provided for connection to a local earth. Supply Requirements - 90V-264V
- 45-65Hz
- 1ph
- 300VA max
Temperature Range - Storage: -20°C to 60°C
- Operating: 0°C to 45°C
Lead Set Specifications - 1 x 3m 4 core output lead terminated in 4mm plugs
- 2 x 3m 2 core timer lead terminated in 4mm plugs
Dimensions and weight Modes of Operation Output Adjust This mode allows full control of frequency, voltage and phase. Each voltage, phase and frequency can be controlled together or independently. All parameters are continuously variable using the adjust control, and step changes of any value may be made. The timer automatically resets and starts when a step change of value is entered, and stops if either contact input changes state. Step changes of phase for testing Vector Surge relays are easily generated in this mode. - Frequency Range: 30-999.99Hz
- Frequency Resolution: 0.01Hz
- Frequency Accuracy: ±0.05%rdg+2d
- Phase Resolution: 0.1º
- Phase Accuracy: ±0.3º phase to phase
Phase Lock Mode The frequency and phase of the output can be controlled by an external reference in phase lock mode. The reference may be the mains supply to the ART3V, or an external voltage or current. This mode allows testing of directional and distance protection in conjunction with an external current source. - Phase Lock Range: 45-65Hz
- External Voltage Ref: 20-250V AC
- External Current Ref: 0.2-5A AC
- Phase Resolution: 0.1º
- Phase Accuracy:
- ±0.3º phase to phase
- 3.0º reference to output
Fault Config Mode
Fault Config mode allows extra flexibility in testing complex timed events or several sets of values that must be applied to a relay in turn. This mode allows three sets of values to be set in advance (pre-fault, fault, and post-fault values). The ART3V may be set to switch from one state to the next on a change of contact or after a specific time. In addition, the timer may be set to start or stop on any one of the state changes or a change of contact state. This mode allows frequency, phase and voltage to be changed simultaneously if required. df/dt and ROCOF (Rate Of Change Of Frequency) Loss of mains protection often takes the form of a df/dt relay, sensitive to the rate of change of frequency over time. The ART3V is able to generate a swept frequency output with accurate rates of change of frequency between preset frequencies. The rate of change may be continuously varied to find the relay setting or stepped to time the relay. The output may be set to either sweep continuously or generate single sweeps with timing. - Frequency Range: 45 - 70Hz
- Frequency Resolution: 0.01Hz
- ROCOF Range: 0.001 - 10.000Hz/s
- ROCOF Resolution: 0.001Hz/s
|