Megger MVC1010 Voltage Clamp

SKU: MEGGMVC1010
  • Voltage transformer measures current via iron-nickel magnetic clamp
  • Compatible with various Megger earth testers
  • Measures AC current from 1mA to 1000A with ±0.3% accuracy
More Info
In Stock - Available Next Day

Megger MVC1010 Voltage Clamp

The Megger MVC1010 Voltage Clamp is a useful attachment that is compatible with selected Megger earth testing instruments. It is used as a voltage transformer and takes non-contact AC current measurements from 1mA to 1000A. Accuracy stands at ≤0.3% at full range with phase shift of 0.7˚ and a best resolution of 1mA.

The Megger MVC1010 has a magnetic Fe-In core in its large clamp and can clamp onto conductors with diameters of up to 52mm. It is suitable for attached rod technique and stakeless testing and it has a 1:1000 step-down ratio across its primary and secondary coils. It is suitable for measuring current across a single phase of an installation and can even measure resistance when used together with the Megger MCC1010 Clamp.

The Megger MVC1010 is rated as Cat IV 600V according to EN61010 and is safe to use thanks to a protective voltage limiting circuit that always keeps touch voltage at safe levels when the clamp is used correctly.

Megger part number: 1010-518

Key Features

  • CAT IV 600 V current measurement to 1000 A AC
  • Accuracy: ≤0.3% (at full range)
  • Max resolution: 1mA
  • Phase shift: ≤0.7˚ (at full range)
  • Iron-nickel permeable magnetic core
  • 52mm max clamping diameter
  • Compatible with Megger earth testers
Specification

Electrical

  • Step-down current ratio: 1000:1
  • Sensitivity: 1mA/1A
  • Primary current ranges: 1m to 100mA; 0.1A to 1A; 1A to 10A; 10A to 100A; 100A to 1000A
  • Accuracy of output signal: ≤1% + 5µA; ≤1% + 5µA; ≤1% + 5µA; ≤0.5%; ≤0.3%
  • Phase shift of output signal: Not specified; 0.7˚; 0.7˚; 0.7˚; 0.7˚
  • Maximum continuous current: 1000A at ≤500Hz; 100A at >500Hz
  • Frequency bandwidth: 15Hz to 10kHz
  • Crest factor: ≥6 for current up to 2000A peak (300A RMS)
  • Influence of crest factor: ≤1% for CF≤4
  • Nominal load impedance: ≤1Ω (burden resistance)
  • Maximum output voltage: ≤28 V peak (electronic limiter)
  • Influence of frequency: 30Hz - 5kHz ≤0.25%
  • Influence of conductor position in the jaws: ≤0.3% of amplitude
  • Load influence up to 5Ω: Amplitude within specification up to 900A; ≤0.25% of amplitude above 900A; ≤0.1˚ on phase
  • Influence of DC offset: ≤2% up to 20A DC
  • Working voltage: ≤600V RMS

Environmental

  • Operating temperature: -20˚C to +50˚C, <85% RH
  • Storage temperature: -40˚C to 70˚C, <85% RH
  • Influence of temperature: ≤0.1% on amplitude phase within specification
  • Influence of humidity: Amplitude and phase within specification (excludes ice and dirt on the jaws)
  • Max conductor diameter: 52mm

General

  • Casing protection: IP40 with jaws closed
  • Operating altitude: 2000m
  • Output terminals: 4mm shrouded sockets
  • Electrical safety: IEC 61010-1:2010 +; IEC 61010-2-030:2010 +; IEC61010-2-032:2002 
  • EMC: IEC61326-1
  • Safety: Cat IV 600V pollution degree 2
  • Weight: 700g
  • Dimensions: 45mm x 110mm x 218mm
Label Type Size Download
pdf Megger MCC1010/MVC1010 Current Clamp Datasheet pdf 256.8 KB Download