BAUR PGK25-UK 25kV DC test set supplied with 3.5m HV Lead & Discharge Rod

SKU: BAURPGK25UK
  • A transportable and versatile high-voltage tester with negative polarity, which has been designed for numerous tests to be executed with precision and ease
  • The PGK25 can run on-site testing of paper-insulated mass-impregnated cables, voltage testing and cable sheath testing, with the results then able to be analysed
  • The Voltage Tester will automatically power off at the end of testing, preserving battery life for future tests and ensuring several tests can be taken on each charge
More Info
Typically ships in 2-3 weeks

BAUR PGK25-UK 25kV DC test set supplied with 3.5m HV Lead & Discharge Rod

The BAUR PGK25 DC High Voltage Tester is a mobile, compact and versatile high-voltage tester with negative polarity. Expertly designed for the testing of paper-insulated mass-impregnated cables and electrical equipment in medium-voltage networks, the tester is able to perform tests that can meet a wide variety of standards, which are:/p>

  • On-site testing of paper-insulated, mass-impregnated cables: EEE 400-2012 and IEC 60060-3
  • Voltage tests on electrical equipment: IEEE 62.2 and IEEE 95
  • Cable sheath testing: IEC 60502 / IEC 60229 and VDE DIN 0276-620/621

On top of this, the PGK25 has an in-built ammeter with five measurement ranges, which span from 1µA to 10mA, as well as a timer which can set times between 1 minute and 30 minutes. It is also able to conduct voltage measurements directly at the HV output and features two continuously variable DC voltage ranges, which are 0 to 5kV and 0 to 25kV.

The PGK25 is able to switch off automatically at the end of testing, with a discharge resistance that is designed for maximum discharge energy of 5000J. The tester also includes a switch-on interlock, and is optimised for mobile applications. Powered by a 12V rechargeable battery, it can also be powered using a 12V supply or mains supply.

Baur part number: PGK25-UK

Key Features

  • Can conduct on-site testing of paper-insulated mass-impregnated cables, as well as voltage testing on electrical equipment and cable sheath testing
  • Has two continuously adjustable voltage ranges of DC 0-5kV and DC 0-25kV
  • Integrated timer for setting the test time
  • An inbuilt ammeter with 5 measurement ranges from 1µA to 10mA
  • Can be powered with a battery, and external 12V power supply, or a mains voltage
  • Can be connected to an external curve tracer for recording test current
  • Can measure voltage directly at the HV output
  • Automatically switches off at the end of testing
  • Switch-on interlock

What's In The Box?

  • BAUR PGK25 DC High Voltage Tester
  • Discharge Rod
  • 3.5m HV Lead
  • 2.6m HV Connection Cable
  • 3m Earth Cable with Earth Terminal
  • 2.5m Mains Supply Cord
  • User Manual
Specification

Testing

  • DC Voltage (negative) -
    0-5kV
    0-25kV
  • Output Current (negative) - 1mA
  • Short-Circuit Current (negative) - 3mA
  • Voltage Measurement Range -
    Range I 0-5kV
    Range II 0-25kV
  • Current Measurement Range - 50nA to 1µA / 10µA / 100µA / 1mA / 10mA
  • Maximum Discharge Energy -
    For 1 discharge/10 min 3000J, 9.6µF / 25kV
    For 1 discharge/20 min 5000J, 16µF / 25kV

Integrated Rechargeable Battery

  • Battery Type - Lead-acid battery DC 12V, 6.5Ah (maintenance free)
  • Battery Life - Approximately 30 min at 2/3 load
  • Charging Time - Approximately 24h

General

  • Power Supply -
    Mains Voltage - 110/120V, 220/230V, 240V, 50/60Hz
    Integrated Rechargeable Battery - Lead-acid battery DC 12V, 6.5Ah (maintenance free)
    External Supply - DC 12V
  • Power Consumption - 110VA
  • Ambient Temperature (Operational) - 0°C to +45°C
  • Storage Temperature - -20°C to +60°C
  • Relative Humidity - Non-condensing
  • Dimensions (W x H x D) - Approximately 415 x 140 x 360mm
  • Weight - Approximately 16.5kg
  • Safety and EMC - CE-compliant in accordance with Low Voltage Directive (2014/30/EU), EMC Directive (2014/30/EU), EN 60068-2-ff Environmental Testing