Chauvin Arnoux CA6472/CA6474 Pylon Tower Earth Testing Kit

SKU: CHAUPO1299930
  • Used for quick testing of all earthing systems, with ease and guaranteed accuracy
  • The kit has the capabilities of running numerous tests, and has an automatic and expert mode
  • The CA6472 allows for the testing of pylons, which limits disruption and difficulty
More Info
Typically ships in 5-7 working days

Chauvin Arnoux CA6472/CA6474 Pylon Tower Earth Testing Kit

The CA6472 earth and resistivity tester can be used for quick, comprehensive, and accurate testing of all earting systems. When used alongside the CA6474, its capabilities are expanded and it can offer pylon earth measurements, making it the ideal tool for the maintenance of pylon systems. With a frequency range of 41 to 5,078Hz, the CA6472 allows for the analysis of an earthing system's frequency behaviour.

Complete all types of earth resistance measurements and earth measurements on pylons, as well as earth coupling, ground potential measurement, and continuity/resistance. The 3P earth measurement method is the traditional method of using rods to measure the resistance of an existing earth connection, and the kit allows the user to perform this.

With both an automatic and expert mode, the user can opt for either of the two modes:

  • Automatic mode - the CA6472 has a single key for simple handling, with a simple STOP/START button and the selection of function by rotary switch. The instrument will carry out a default measurement at 128Hz, and then chooses the most appropriate frequency.
  • Expert mode - users can choose the required measurement parameters (specific measurement frequency, frequency scan, measurement voltage between H and S, etc.) and can access additional measurement results for more accurate interpretation. It also automatically recognises input connections.

The CA6472 can be used in conjunction with the CA6474 to perform earth measurements on pylons, which would otherwise be impossible with traditional 3P methods, unless the dangerous and time-consuming process of disconnecting the earth cable is done. With 4 current sensors positioned around the footings of the pylon, and a frequency scan up to 5kHz, it is possible for the user to measure the earth impedance of the pylon precisely and selectively.

The kit is also provided with the P01102024 Earth Tester Kit, which enhances the capabilities of the CA6472 and CA6474.

Chauvin Arnoux part number: P01299930

Key Features

  • Can perform all types of earth resistance measurements and earth measurement on pylons
  • Can analyse the frequency behaviour of earthing systems (41Hz to 5kHz)
  • Wide measurement range for optimum resolution
  • Automatic calculation of the earth coupling coefficient and ground resistivity
  • Can record results
  • Has both an automatic and expert mode

What's In The Box?

Supplied with the CA6472:

  • Mains adaptor
  • 2-pole mains cable for recharging the battery from the mains supply
  • One operating manual in 5 languages on CD-ROM
  • 5 simplified operating manuals and 5 specific lables (different languages)
  • Data export software
  • USBoptical communication cable
  • Two C182 clamps

Supplied with the CA6474:

  • Carrying bag for accessories
  • One CA6472/CA6474 connection lead
  • 6 BNC/BNC cables (15m long)
  • 4 AmpFLEX flexible current sensors (5m long)
  • 1 set of 12 AmpFLEX identification rings
  • 2 cables (5m green, 5m black) with safety connectors on winder
  • 5 spade lug/banana plug converters (4mm)
  • 3 clamps
  • 1 calibration loop
  • 5 operating manuals and 5 specific labels (different languages)

Supplied with the P01102024 Earth & Resistivity Kit:

  • 4 stakes
  • 4 different coloured reels of cables (50m, 100m or 150m long)
  • 1 mallet
  • 5 spade lug/banana plug adaptors
  • Carrying bag
  • 4 x 4mm banana cables
  • 4 crocodile clips
  • 2 test probes
Specification

Electrical Specifications

3P Method

  • Range - 0.01Ω to 99.9kΩ
  • Resolution - 0.01 to 100Ω
  • Accuracy - ± (2% + 1 count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Frequency - 41 to 5,078Hz
  • Coupling Measurement - yes
  • Auxiliary Rod Resistance Measurement - 0.1Ω to 100kΩ
  • Uinterference - Maximum 60Vpeak
  • Test Method - -
  • Type of Measurement - 3 wires
  • Measurement Current - -

4P/4P Selective Method

  • Range - 0.001Ω to 99.99Ω
  • Resolution - 0.001Ω to 10Ω
  • Accuracy - ± (2% + 1 count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Frequency - 41 to 5,078Hz
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - 0.01Ω to 100kΩ
  • Uinterference - Maximum 60Vpeak
  • Test Method - -
  • Type of Measurement - 4 wires
  • Measurement Current - -

Earth Measurement with 2 Clamps

  • Range - 0.01Ω to 500Ω
  • Resolution - 0.01 to 1Ω
  • Accuracy - ± (10% + 1 count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Voltage - Auto: 1,367Hz; Manual: 1,367Hz; 1,611Hz: 1,758Hz
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - -
  • Uinterference - Maximum 60Vpeak
  • Test Method - -
  • Type of Measurement - -
  • Measurement Current - -

Resistivity

  • Range - 0.01kΩ to 99.9kΩ
  • Resolution - 0.01 to 100Ω
  • Accuracy - ± (2% + 1 count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Frequency - 41 to 128Hz
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - -
  • Uinterference - Maximum 60Vpeak
  • Test Method - Wenner and Schlumberger with automatic calculation
  • Type of Measurement - 4 wires
  • Measurement Current - -

Earth Potential Measurement

  • Range - 0.01mV to 65.00V
  • Resolution - 0.01mV to 10mV
  • Accuracy - ± (5% + 1 count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Frequency - 41 to 128Hz
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - -
  • Uinterference - Maximum 60Vpeak
  • Test Method - -
  • Type of Measurement - 3 wires
  • Measurement Current - -

DC Resistance Measurement

  • Range - 0.001Ω to 99.9kΩ
  • Resolution - 2 wires: 0.01Ω to 100Ω; 4 wires: 0.001Ω to 10Ω
  • Accuracy - ± (2% + 2 counts)
  • No-load Voltage - ±16 VDC
  • Measurement Frequency - DC
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - -
  • Uinterference - -
  • Test Method - -
  • Type of Measurement - 2 wires or 4 wires
  • Measurement Current - >200mA DC

Measurements with C.A6474

  • Range - 0.001Ω to 99.99kΩ
  • Resolution - 0.001 to 10Ω
  • Accuracy - ± (5% + 1count)
  • No-load Voltage - 16 or 32Vrms
  • Measurement Frequency - 41 to 5078Hz
  • Coupling Measurement - -
  • Auxiliary Rod Resistance Measurement - 0.01Ω to 100kΩ
  • Uinterference - Maximum 60Vpeak
  • Test Method - -
  • Type of Measurement - -