Kewtech KEW MATE 2012RA Multimeter

SKU: KEWTKEW2012RA
  • Measures AC/DC voltage up to 600V, current up to 120A & resistance up to 60MΩ
  • Has high accuracy with True RMS function
  • Supplied with a built-in 12mm AC/DC clamp sensor
More Info
In Stock - Available Next Day

Kewtech KEW MATE 2012RA Multimeter

The Kewtech KEW MATE 2012RA Multimeter is a compact and pocket-sized True RMS digital multimeter featuring small built-in 12mm clamp jaws that are great for navigating narrow wiring spaces such as distribution boards and control panels.

The 2012RA measures AC/DC voltage up to 600V, current up to 120A, resistance up to 60MΩ, and capacitance up to 40μF, as well as frequency, continuity, and diode testing. The 2012RA supports True RMS measurements for distorted waveforms and includes a buzzer that provides an audible warning below 35Ω, along with a responsive analogue-style bar graph for dynamic readings.

Additional features include a USB output for data logging, auto and manual ranging, data hold, relative mode, peak/min/max memory, and auto power-off to preserve battery life. The 2012RA is CAT III 300V / CAT II 600V safety rated, offering reliable and safe performance in demanding electrical environments.

part number: KEWMATE2012RA

Key Features

  • True RMS measurements
  • AC and DC voltage up to 600V
  • AC and DC current up to 120A
  • Resistance up to 60MO
  • Continuity test buzzer (warns below 35O)
  • Conductor size ø12 mm max
  • Capacitance up to 40µF
  • Diode test function
  • Capacitance measurement
  • Frequency measurement
  • Continuity buzzer
  • Bar graph indicator
  • Data hold memory function
  • Resistance measurement
  • Relative function
  • Auto and manual ranging
  • Display: 6000 counts

What's In The Box?

  • Kewtech KEW MATE 2012RA Multimeter
  • 2 x R03(AAA) Batteries
  • User manual
Specification
  • DC V:
    600.0mV/6.000/60.00/600.0V (Input impedance: approx. 10MΩ)
    ±1.0%rdg±3dgt
  • AC V:
    6.000/60.00/600.0V (Input impedance: approx. 10MΩ)
    ±1.5%rdg±5dgt (45 - 400Hz)
  • DC A:
    60.00/120.0A
    ±2.0%rdg±8dgt (60A)
    ±2.0%rdg±5dgt (120A)
  • AC A:
    60.00/120.0A
    ±2.0%rdg±5dgt (45 - 65Hz)
  • Ω:
    600.0Ω/6.000/60.00/600.0kΩ/6.000/60.00MΩ
    ±1.0%rdg±5dgt (600Ω/6/60/600kΩ)
    ±2.0%rdg±5dgt (6MΩ)
    ±3.0%rdg±5dgt (60MΩ)
  • Continuity Buzzer: Buzzer sounds below 35±25Ω
  • Diode Test
    2.000V ±3.0%rdg±5dgt
    Open-loop voltage: approx. 2.7V
  • Capacitance:
    400.0nF/4.000/40.00μF
    ±2.5%rdg±10dgt
  • Frequency:
    (AC A) 99.99/400.0Hz
    ±0.2%rdg±2dgt (100Hz)
    ±0.1%rdg±1dgt (400Hz)
    (AC V) 99.99/999.9Hz/9.999/99.99/300.0kHz
    ±0.2%rdg±2dgt (100Hz)
    ±0.1%rdg±1dgt (1000Hz/10/100/300kHz)
  • Input Sensitivity:
    Current: more than 6A
    Voltage: more than 6V [-10kHz]/more than 20V [10k - 300kHz]
  • Conductor Size: ø12 mm max
  • Applicable Standards:
    IEC 61010-1 CAT III 300V
    CAT II 600V Pollution degree 2
    IEC 61010-2-032
    IEC 61010-031
    IEC 61326-1
    EN 50581(RoHS)
  • Power Source
    R03(AAA)(1.5V) x 2
    * Continuous measuring time: DC V: approx. 150 hours, AC A: approx. 25 hours
    (Auto power save: approx. 15 minutes)
  • Dimensions: 128(L) x 92(W) x 27(D) mm
  • Weight: 220g approx. (including batteries)