T & R 100 ADM Main Output The main output on the unit has four taps, allowing the selection of output voltages up to 240V and output currents up to 200A. | | Current | Output @230V | | Range | Continuous | 5 min* | 1 min* | | O/CV | Load V | | 10V | 33A | 67A | 100A | | 10.6V | 8.7V@100A | | 35V | 10A | 20A | 30A | | 36V | 32V@30A | | 100V | 3A | 6A | 10A | | 108V | 99V@10A | | 240V | 1A | 2A | 3A | | 276V | 259V@3A | | 240Vdc | 1A | 2A | 3A | | | | *Off time of 15 minutes. On times based on an ambient temperature of 25°C. Protection: over current trip, duty cycle trip, thermal monitoring. I Limit Mode The main output has a current limit mode that gives very fine control of output currents up to 10A. It also allows fine current control into very low impedance loads such as digital relays. | | Current | Output @230V | | Range | Short Circuit | Continuous | 5min | 2min | O/CV | Load V | | 10V | 10A | 3A | 6A | 10A | 8.6V | 5V@6A | | 35V | 3A | 1A | 2A | 3A | 29V | 132V@30A | | 100V | 1A | 0.3A | 0.6A | 1A | 88V | 99V@10A | | 240V | 0.3A | 0.1A | 0.2A | 0.3A | 224V | 259V@3A | Auxiliary DC Output | Range | Maximum A | Continuous Rating | | 24V | 1A | 25W | | 48V | 1A | 25W | | 60V | 1A | 25W | | 110V | 0.23A | 25W | | 220V | 0.23A | 25W | Protection: current limit Fixed AC Output | Output Voltage | Current | | 110V | | 300mA | Protection: fuse. Metering The 100ADM output is metered by a digital true RMS system with a single cycle capture memory ammeter—whenever the timer stops and the output is switched off, the current reading is held on the display. The RMS value of a single cycle can be captured. A current trip is set to 110% of full scale of the selected metering range. | Range | Resolution | Trip current | Accuracy | Aquisition time | | 2.000A | 0.001A | 2.1A | ±0.5% rdg±5d | 20ms | | 10.00A | 0.01A | 10.5A | ±0.5% rdg±5d | 20ms | | 20.00A | 0.01A | 21A | ±0.5% rdg±5d | 20ms | | 100.0A | 0.1A | 105A | ±0.5% rdg±5d | 20ms | Timing System | Range | 0-999.999s/9999.99s/99999.9s autoranging | | Resolution | 1/10/100ms | | Accuracy | 0.01%rdg+2d (+4d current operated mode) | | Contact o/c | 24V | | Contact s/c | 20mA | | Vdc | 24—240V | Each contact circuit will auto-select for normally open or normally closed contacts. A DC voltage of 24—240Vdc may also be used to trigger either timer channel. Contact state is shown by an LED. Supply Requirements 115V/230V ±10% auto-selecting 50/60Hz 1ph 1100VA max. Safety An earth terminal is provided for connection to a local earth. The unit is designed to comply with BSEN61010 and is CE marked. Temperature Range Storage -20°C to 60°C Operating 0°C to 45°C Standard Accessories The T and R 100ADM mk4 is supplied with operating manual, mains lead and, output lead set and spare fuses. Optional Accessories 100ADM-F filter unit, RB10 resistor box, printer kit, ADMlog software. The unit is supplied as standard in an aluminium case with removable lid. The unit is also available in a plastic Pelicase as an option. Please note that the Pelicase lid is not removable. Weights and Dimensions | T and R 100ADM | Dimensions | Weight | | Pelicase unit | 560mm x 456mm x 265mm | 23.3kg | |