Fluke 1672 Multifunction Tester

The Fluke 1672 Multifunction Tester with its compact and ergonomic design, users are able to verify electrical installations in domestic, commercial and industrial applications whilst meeting industry standards including IEC/HD 60364-6, the 1672 offers an integrated installation testing solution. With a full colour touchscreen, the 1672 has a user friendly interface without the complexity of multi level menus that can be navigated even whilst wearing gloves. The rotary dial can also be used to navigate through the display.

Perform All Required Tests up to 30% Faster

With accurate installation testing and efficiency the 1672 offers the operator an automatic pass/fail result allowing for fast and accurate testing to be conducted. Further testing that can be conducted by the 1672 includes the simultaneous readings of voltage measurements between L-N, L-PE using the main cords meaning no change of measurement connections is required.

The Fluke 1672 is able to measure trip time and current RCD type AC, A and F in one test with RCD variable test current and Automatic RCD test sequence testing also been able to be performed. The on on/off switchable Auto start for continuity, RCD and loop tests. Further features include the zero adapter that allows for fast, reliable and accurate test lead and mains cord compensation

The Fluke 1672 can provide measurements for Voltage AC, DC and frequency, insulation resistance, loop and line impedance, prospective earth fault current (PEFC/IK), prospective short circuit (PSC/IK), RCD trip time, RCD trip current (ramp test), and earth resistance in addition to performing continuity tests, RCD tests, wiring polarity checker that detects broken PE and N wires, and continuity tests with a low test current (10mA) to measure motor windings. Insulation resistance measurements can be performed at 100V/250V/500V/1000V, insulation at L-N, L-PE, N-PE inputs 250 V, 500V, 1000 V.

Optimized Software and Reporting with Fluke TruTest Software

The 1672 is compatible with the Fluke TruTest Software (optional extra) that provides a simple electrical system data management and reporting. TruTest allows the creation and transfer of data between the software and tester via USB-C to ensure accurate results. The report builder provides users the ability to quickly format measurement data into printable test certificates and reports, with company logos and signatures also available to be added.

The 1672 boasts a rechargeable lithium ion battery (via USB-C charging point) for a full days use in the field, with a padded neck strap included for comfort and to allow hands free operation. and has colour coded input terminals that are CAT III 600V and CAT IV 300V rated. The Fluke 1672 is updatable in the field allowing for any changes in regulations or enhancements to the tester to be conducted. The provided hard case provides users with protection of their tester in transporting and stopping the tester.

For even more detailed discussion about the 1670 range, watch our podcast episode below

Fluke 1660 Series and 1670 Series Comparison

  1662 1663 FC 1664 FC 1672 FC 1673 FC 1674 FC
Full Colour touch screen      
Li-ion Battery      
USB-C/BLE interface supports charging and data transfer       USB-C USB-C/BLE USB-C/BLE
Digital rotary dial - supports new feature additions      
Form Capture      
Project Setup      
Field updatable      
Bi-directional data      
660V maximum voltage, 600V volt operation      
Auto pass/fail limits      
Onscreen helps      
Voltage drop measurement      
Insulation monitoring device (IMD) test          
Surge Protection Device (SPD) test          
Save results from additional Fluke Connect tools        
User programmable Auto test sequence        
Wiring polarity checker, detects broken PE and N wires
Insulation resistance
Continuity and resistance
Measure motor windings with continuity test (at 10mA)
Loop and line impedance
Prospective Earth Fault Current (PEFC/IK)
Prospective Short-Circuit Current (PSC/IK)
RCD trip time/RCD trip current (ramp test)
Measure trip time and current for RCD type AC, A and F in one test
RCD variable test current
Automatic RCD test sequence
Phase sequence test
Voltage AC, DC and frequency AC only
Insulation at L-N, L-PE, N-PE inputs 250V, 500V, 1000V 250V, 500V, 1000V 50V, 100V, 250V, 500V, 1000V 100V, 250V, 500V, 1000V 50V, 100V, 250V, 500V, 1000V 50V, 100V, 250V, 500V, 1000V
Continuity at L-N, L-PE, N-PE inputs  
EV Test 6mA DC (RCD A/EV, RCD B/Mi, RCD-DD)    
Test smooth DC sensitive RCDs (Type B/B+)    
Earth resistance    
Standard Auto Test Sequence        
Insulation PreTest after function      
Loop and line impedance - mΩ resolution        
Auto pass/fail results      
Fluke Connect compatibility    
Fluke Cloud Storage    
On/Off switchable Auto Start for continuity, RCD and loop test
USB-C/BLE interface IR-USB IR-USB/BLE IR-USB/BLE USB-C USB-C/BLE USB-C/BLE
Memory
Z Max memory    
Illuminated display

Fluke part number: 5580852

Key Features

  • Colour touchscreen and rotary knob for fast navigation of the menus
  • Simultaneous readings of voltage measurements between L-N, L-PE and N-PE using the mains cord without having to change the measurement connections
  • RCD trip current and trip time measurement
  • Prospective earth fault current (PEFC/IK), prospective short circuit (PSC/IK)
  • RCD trip time, RCD trip current (ramp test)
  • Continuity tests with a low test current (10mA) to measure motor windings
  • Wiring polarity checker that detects broken PE and N wires
  • Voltage AC/DC testing
  • Insulation
  • Phase rotation
  • Voltage Drop
  • Zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Hard case for transportation and storage of the device
  • Rechargeable battery with standard USB-C charging port
  • Compact and lightweight with padded neck strap to free hands
  • Can be updated in the field

What's In The Box?

  • Fluke 1672 Multifunction Tester
  • Heavy duty mains cord with single input connector
  • Hard case
  • USB-C power adapter for charging
  • Remote control probe
  • Hanging strap
  • Zero adapter
  • Test leads and probes
  • Alligator clips
  • Li-Ion battery
Specification

Specifications

  • Size: 26.25cm x 14.19cm x 11.93cm (10.3 x 5.6 x 4.7in)
  • Weight (including batteries)1.6KG (3.5lb)
  • Battery size, quantity: B290, Li-ion, 10.8V, 2500 mAH, 27 Wh
  • Ingress Protection: IEC 60529; IP40
  • Safety: Complies with IEC/EN 61010-1, IEC 61010-2-030, IEC 61010-2-034
  • Safety rating: CAT III 600 V, CAT IV 300 V
  • Performance: IEC 61557-1 to IEC/EN 61557-8 and IEC 61557-10

Voltage measurement AC, DC and Frequency

  • Range: 600V
    Resolution: 0.1V
    Input Impedance: 320 kΩ
    Overload Protection: 660V
  • Range: 45-66Hz
    Resolution: 0.1Hz
    Input Impedance: 320 kΩ

Continuity testing (RLO)

  • Range (Auto ranging): 20Ω/200Ω/2000Ω
    Resolution: 0.01 Ω/0.1 Ω/1 Ω
    Open Circuit Voltage: >4V

Insulation Resistance measurement (Riso)

  • Test Voltages: 100-250-500-1000V
  • 50V:
    Insulation Resistance Range: 10 kΩ to 50 MΩ
    Resolution: 0.01 MΩ
    Test Current: 1 mA @ 50 kΩ
  • 100V:
    Insulation Resistance Range: 10 kΩ to 20 MΩ
    Resolution: 0.01 MΩ
    Test Current: 1 mA @ 100 kΩ
  • 100V:
    Insulation Resistance Range: 20 kΩ to 100 MΩ
    Resolution: 0.1 MΩ
    Test Current: 1 mA @ 100 kΩ
  • 250V:
    Insulation Resistance Range: 10 kΩ to 20 MΩ
    Resolution: 0.01 MΩ
    Test Current: 1 mA @ 250 kΩ
  • 250V:
    Insulation Resistance Range: 20 kΩ to 200 MΩ
    Resolution: 0.1 MΩ
    Test Current: 1 mA @ 250 kΩ
  • 500V:
    Insulation Resistance Range: 10 kΩ to 20 MΩ
    Resolution: 0.01 MΩ
    Test Current: 1 mA @ 500 kΩ
  • 500V:
    Insulation Resistance Range: 20 kΩ to 200 MΩ
    Resolution: 0.1 MΩ
    Test Current: 1 mA @ 500 kΩ
  • 500V:
    Insulation Resistance Range: 200 kΩ to 500 MΩ
    Resolution: 1 MΩ
    Test Current: 1 mA @ 500 kΩ
  • 1000V:
    Insulation Resistance Range: 100 kΩ to 200 MΩ
    Resolution: 0.1 MΩ
    Test Current: 1 mA @ 1MΩ
  • 1000V:
    Insulation Resistance Range: 200 kΩ to 1000 MΩ
    Resolution: 1 MΩ
    Test Current: 1 mA @ 1MΩ

Surge Protection Device (SPD) Insulation RAMP Test (Varistor Test) IEC 61643-11

  • Test Voltage: 500V:
    Voltage ranges: Step Ramp 0V to 500V
    Resolution: 1V
    Test Current: 1mA
    Accuracy: ± (1.5 % + 3 digits)
  • Test Voltage: 1000V:
    Voltage ranges: Step Ramp 0V to 1000V
    Resolution: 1V
    Test Current: 1mA
    Accuracy: ± (1.5 % + 3 digits)

Insulation Monitoring Devices (IMD) IEC 61557-8

  • Range: 1 kΩ to 10 kΩ
    Resolution: 1 kΩ
  • Range: 10 kΩ to 100 kΩ
    Resolution: 10 kΩ
  • Range: 100 kΩ to 3 mΩ
    Resolution: 100 kΩ
  • Please note: > 1 MΩ only available with voltages >100 V

Loop and line impedance (ZI No Trip and Hi Current)

  • Range setting: 10 Ω
    Resolution: 0.001 Ω
    Accuracy: Hi Current mΩ mode: ± (2 % + 35 digits)/No Trip (2&3 wire) mode: ± (3 % + 6 digits)
  • Range setting: 20 Ω
    Resolution: 0.01 Ω
    Accuracy: Hi Current mode: ± (2 % + 4 digits)
  • Range setting: 200 Ω
    Resolution: 0.1 Ω
    Accuracy: No Trip mode: ± (3%)/Hi Current mode: ± (2%)
  • Range setting: 2000 Ω
    Resolution: 1 Ω
    Accuracy: ± 6%

Prospective Earth Fault Current (PEFC) Prospective Short Circuit Current (PSC)

  • Range: 0.0-99.9%
    Resolution: 0.1%
    Accuracy: Consider accuracy of line impedance measurement(s)
  • Note: Voltage drop reading is calculated from line impedance measurement and entered current rating

RCD tests, RCD types tested

  • AC (General, no delay)
  • AC (Time delay)
  • A, F (General, no delay)
  • A, F (Time delay)
  • GFCI

RCD tripping time test (ΔT)

  • x1⁄2, 1:
    10mA
    30mA
    100mA
    300mA
    500mA
    1000mA
    Var
  • x5:
    10mA
    30mA
    100mA
  • Ramp:
    10mA
    30mA
    100mA
    300mA
    500mA
    1000mA
    Var
  • Auto:
    10mA
    30mA
    100mA
  • Mains voltages 50V - 265V ac, 45/66Hz
  • 100mA, 300mA and 500mA: Type B RCDs require main voltage range of 195V to 265V
  • 1000mA: Type AC RCDs only
  • Var: Type A RCDs are limited to 700mA, not available for type B RCDs

RCD Tripping Current (IΔN) Measurement/Ramp Test

  • Current range: 30% of 110% of RCD rated current (1)
    Step size: 10 % of IΔN (2)
    Dwell time Type G: 300 MS/Step
    Dwell time Type S: 500 M/S Step
    Measurement accuracy ±5%
  • (1): Specified trip current ranges (IEC 61008-1):
    30 % to 150 % for Type A IΔ N > 10 mA
    30 % to 210 % for Type A IΔ N = 10 mA
    20%to210%forTypeB
    50 % to 100 % for Type AC
    35%to140%forTypeA(>10mA)
    35 % to 200 % for Type A (≤ 10 mA)
    50 % to 200 % for Type B
  • (2): 5% for Type B

Phase sequence indication

  • Icon: Phase Sequence indicator is active
    Range: 185V to 600V
    Display: "1-2-3: or "3-2-1" for incorrect phase
Label Type Size Download
pdf Fluke 167X Multifunction Tester Datasheets pdf 3.3 MB Download

Please see our terms and conditions for full details of TM Care & Protect.

Everything you’re likely to require for the next 3 or 5 years:

✅ Annual calibrations included
No further calibration costs for either 3 or 5 years

✅ Free collection and return for annual calibration
No hidden postage costs when it’s time for calibration

✅ ‘Zero-Downtime’ for the life of your care plan
Free loan equipment should your purchase ever need sending away for repair

✅ Anti-theft protection 
Each care plan includes a SmartTrace Forensic Marking kit that acts as a deterrent for your test equipment and other tools

✅ Instrument cleaning kit
Cleaning kit included with each TM Care & Protect plan

Our hope is that TM Care & Protect will bolster our commitment to support you throughout your journey with us, providing you peace of mind from the hassles of annual servicing, potential tool theft and loss of earnings.

Ensures complete reliability, minimised downtime and peace of mind. TM Care & Protect packages include:

✅ Annual Calibration
No further calibration costs for up to 5 years.

✅ Zero Unplanned Downtime
In case of any unforeseen repairs, we provide FREE loan instruments so you can continue working.

✅ Theft Deterrent Kit
Each care plan includes a SmartTrace forensic marking kit: The UK's most powerful theft deterrent. Use on your test equipment, van and tools.

✅ No Shipping Cost
Includes collection and return deliveries when it's time for calibration.

✅ Instrument Cleaning Kit
Avoid preventable issues by keeping your test equipment clean.

Our hope is that TM Care & Protect will bolster our commitment to support you throughout your journey with us, providing you peace of mind from the hassles of annual servicing, potential tool theft and loss of earnings.

Please see our terms and conditions for full details of TM Care & Protect.