The Fluke 6500-2 PAT Tester is a smart portable appliance tester that stands out because of its simple one button test function and its sleek, lightweight design. A wide range of tests are available on the instrument including power-on, earth bond and insulation testing. Current testing options are touch current and substitute leakage current whilst the instrument can also check RCD trip current and RCD trip time. A series of load/leakage tests can also be carried out with the 6500-2. These include load current, load power, leakage current and PELV tests.

Aside from comprehensive measurement capabilities, the Fluke 6500-2 has several useful design features that make it extremely practical. Firstly, the large, colour, graphical display makes measurements easy to see and also shows useful help screens when carrying out PAT tests. Simple push buttons and a one-button test trigger make the test process simpler. Just one mains socket can be used for all testing functions whilst an IEC socket facilitates tests on mains and extension cables. A built-in handle makes the tester easy to move whilst all accessories fit into the handy carry case.

The smart capabilities of the Fluke 6500-2 also enable speedier, more streamlined testing. A USB stick and cable are supplied as standard and both can download data from the tester’s large internal memory which has space for over 1000 results. A professional testing mode allows quick testing and a full QWERTY keyboard helps the user quickly enter data including shorthand codes for locations, integral sites, and descriptions.

The Fluke 6500-2 is supplied with all necessary accessories including a mains cord, test leads, test probes and crocodile clips. It offers the user flexible, portable PAT testing and is rated as Cat II 300V.

Key Features

  • Power-on test
  • Earth bonding test
  • RCD trip current and trip time test
  • Load/leakage tests
  • PELV test
  • Colour, graphical display
  • Internal memory with space for >1000 readings
  • Single mains and IEC sockets
  • USB stick and cable included
  • Carry case

What's In The Box?

  • Fluke 6500-2 PAT Tester
  • Instruction manual
  • Test leads
  • Test probes
  • Crocodile clips
  • Mains cord
  • Fluke yellow storage case
  • USB stick
  • USB cable
Specification

Power-on Test

  • The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
  • Display Range : 90 V to 264 V
  • Accuracy at 50 Hz: ± (2% + 3 counts)
  • Resolution: 0.1 V
  • Input Impedance: > 1 MΩ // 2.2 nF
  • Maximum Input Mains Voltage: 264 V

Earth Bond Test (Rpe)

  • Display Range: 0 to 19.99 Ω
  • Accuracy (After Bond Test Zeroing): ± (5% + 4 counts)
  • Resolution: 0.01 Ω
  • Test Current: 200 mA AC -0% +40% into 1.99 Ω; 25 A AC ± 20% into 25 mΩ at 230 V
  • Open Circuit Voltage: > 4 V AC, < 24 V AC
  • Bond Test Zeroing: Can subtract up to 1.99 Ω

Insulation Test (Riso)

  • Display Range: 0 to 299 MΩ
  • Accuracy: ± (5% + 2 counts) from 0.1 to 300 MΩ
  • Resolution: 0.01 MΩ (0 to 19.99 MΩ) / 0.1 MΩ (20 to 199.9 MΩ) / 1 MΩ (200 to 299 MΩ)
  • Test Voltage: 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0 % +25 % at 250 kΩ load
  • Test Current: > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
  • Auto Discharge Time: < 0.5 s for 1 μF
  • Max. Capacitive Load: Operational up to 1 μF

Touch Current Test

  • Display Range: 0 to 1.99 mA AC
  • Accuracy: ± (4% + 2 counts)
  • Resolution: 0.01 mA
  • Internal Resistance (via Probe): 2 kΩ
  • Measuring Method: Probe*

Substitute Leakage Current Test

  • Display Range: 0 to 19.99 mA AC
  • Accuracy: ± (2.5% + 3 counts)
  • Resolution: 0.01 mA
  • Test Voltage: 100 V AC ± 20%

Load/Leakage Test: Load Current

  • Display Range: 0 A to 13 A
  • Accuracy: ± (4% + 2 counts)
  • Resolution: 0.1 A*

Load/Leakage Test: Load Power

  • Display Range 230 V Mains: 0.0 VA to 3.2 kVA
  • Accuracy: ± (5 % + 3 counts)
  • Resolution: 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*

Load/Leakage Test: Leakage Current

  • Display Range: 0 to 19.99 mA
  • Accuracy: ± (4% + 4 counts)
  • Resolution: 0.01 mA*

PELV Test

  • Accuracy at 50 Hz: ± (2% + 3 counts)
  • Overload Protection: 300 V rms
  • Warning Threshold: 25 V rms

RCD Test: Trip Current

  • Operational Error: ±10 %
  • Nominal: 30 mA
  • Accuracy: ±5 %

RCD Test: Trip Time

  • Standard Requirement: 61557 Part 6; tolerance of rated test current 0 % to +10 %
  • Operational Error: ±10 %
  • RCD Type: AC general-purpose 30 mA
  • Display Range: 310 ms
  • Resolution: 0.1 ms
  • Accuracy: 3 ms
  • Trip Time Limit at 100 % (30 mA): 300 ms
  • Trip Time Limit at 500 % (150 mA): 40 ms

*The appliance under test is energised at mains voltage.

Environmental

  • Operating Temperature: 0 to 40 °C
  • Relative Humidity: Non condensing < 10 °C / 95% from 10 to 30 °C / 75% from 30 to 40 °C

Safety

  • Safety Rating: Complies with EN61010-1 3rd edition / CAT II, 300 V, pol 2

General

  • Size: 200 mm (L) x 275 mm (W) x 114 mm (H)
  • Weight: 3.13 kg
  • Power Supply: 230 V +10 % -15 %, 50 Hz ±2 Hz or (6500-2 only: 110V +10 % -15 %,50 Hz ±2 Hz)
  • Power Consumption (Tester): 13 W typical (idle) / 60 W max. during 25A Bond test
  • Storage Temperature: -10 to 60 °C
  • Corrosion: 70 °C @ 95 % RH for 5 days max.
  • Operating Altitude: 0 up to 2000 m
  • Sealing: IP-40 (enclosure), IP-20 (connectors)
  • EMC: Complies with EN61326-1, portable
  • EMI Immunity: 3 V/m

Please see our terms and conditions for full details of TM Care & Protect.

Everything you’re likely to require for the next 3 or 5 years:

✅ Annual calibrations included
No further calibration costs for either 3 or 5 years

✅ Free collection and return for annual calibration
No hidden postage costs when it’s time for calibration

✅ ‘Zero-Downtime’ for the life of your care plan
Free loan equipment should your purchase ever need sending away for repair

✅ Anti-theft protection 
Each care plan includes a SmartTrace Forensic Marking kit that acts as a deterrent for your test equipment and other tools

✅ Instrument cleaning kit
Cleaning kit included with each TM Care & Protect plan

Our hope is that TM Care & Protect will bolster our commitment to support you throughout your journey with us, providing you peace of mind from the hassles of annual servicing, potential tool theft and loss of earnings.

Ensures complete reliability, minimised downtime and peace of mind. TM Care & Protect packages include:

✅ Annual Calibration
No further calibration costs for up to 5 years.

✅ Zero Unplanned Downtime
In case of any unforeseen repairs, we provide FREE loan instruments so you can continue working.

✅ Theft Deterrent Kit
Each care plan includes a SmartTrace forensic marking kit: The UK's most powerful theft deterrent. Use on your test equipment, van and tools.

✅ No Shipping Cost
Includes collection and return deliveries when it's time for calibration.

✅ Instrument Cleaning Kit
Avoid preventable issues by keeping your test equipment clean.

Our hope is that TM Care & Protect will bolster our commitment to support you throughout your journey with us, providing you peace of mind from the hassles of annual servicing, potential tool theft and loss of earnings.

Please see our terms and conditions for full details of TM Care & Protect.