Martindale EZ365 Socket, Earth Loop and RCD Tester

SKU: MARTEZ365
  • Verify earth wiring using a non-trip earth loop test and indicating its value in 6 discrete ranges from less than 1.7Ω to 500Ω
  • Check up to 28 socket wiring fault conditions
  • Test for L-NE polarity swap at the incoming supply
More Info
In Stock - Available Next Day

Martindale EZ365 Socket, Earth Loop and RCD Tester

The Martindale EZ365 Socket, Earth Loop and RCD Tester can detect 28 socket wiring faults conditions and check the mains voltage level. Using an earth loop test the EZ365 verifies the earth wiring and indicates the value in 6 discrete ranges from less than 1.7Ω to 500Ω.

The EZ365 identifies socket polarity and earth wiring faults using a combination of red LEDs. Using the three LEDs, each corresponding to neutral, earth and live connections, the user is able to identify common faults, the EZ365 also alerts users to with an audible alarm buzzer should a fault condition be identified.

The EZ365 can check for L-NE polarity swap at the incoming supply and also performs trip tests on 30mA RCDs. Using the L-NE cross polarity test, users can detect serious fault conditions which is easily activated by using the touch pad on the front of the unit. 

The EZ365 is an advanced socket tester as defined by the Health and Safety Executive and is CAT II 300V safety rated.

Martindale EZ165 and EZ365 Comparison table

  EZ165 EZ365
Indicate functional socket
Detect line/neutral reversal
Detect presence of eartht  
Mains Voltage Check
Earth loop impedance
Polarity swap touch test  
30mA RCD trip test  

Key Features

  • Quick and easy main socket polarity testing
  • Earth testing
  • High and low Voltage indication
  • 6 discrete ranges from less than 1.7Ω to 500Ω
  • Non-trip earth loop impedance
  • Robust design for easy removal from a socket
  • Incoming supply polarity swap test
  • Trip testing 30mA RCD
  • Audible indication

What's In The Box?

  • Martindale EZ365 Socket, Earth Loop and RCD Tester
  • EZ365 instruction manual
Specification
  • Nominal Operating Voltage: 230 AC rms
  • Operating frequency: 50Hz
  • Power consumption: <2.5W
  • Power: From Mains socket under test
  • Earth loop threshold accuracy: ± (10% + 0.3Ω) Measurement accuracy can be affected by highly inductive or capacitive loads distributed on the supply
  • Voltage low indication: <195V ± 5%
  • Voltage high indication: >270V ± 5%<
  • Earth neutral voltage Hugh indication: >30V nominal
  • Open earth indication: >500Ω ± 10%
  • RCD test current at 195V: 30mA
  • Duration of RCD test current: 300ms
  • Polarity reversal test: L-NE swap at incoming supply
  • Dimensions: 60 x 80 x 59mm
  • Weight: 93g approx
  • Temperature: -10°C to 40°C, at max. 60% RH
  • Altitude: Up to 2000m
  • Pollution degree: 2
  • Safety: Conforms to BS EN 61010-1, CAT II 300V, Class II, double insulation
  • EMC: Conforms to BS EN 61326-1