Megger DCM305E Earth Leakage Clamp Meter

SKU: MEGGDCM305E
  • Measures earth leakage current and regular current via 40mm clamp
  • True RMS AC current measurement from 0 to 100A
  • Auto hold, peak hold and data hold with low pass filter for stability
More Info
In Stock - Available Next Day

Megger DCM305E Earth Leakage Current Clamp Meter

The Megger DCM305E Earth Leakage Clamp Meter is the ideal instrument for accurately and precisely measuring earth leakage current in addition to other AC current up to 100A AC. It has a resolution of just 0.001mA and excellent accuracy of ±1% (depending on current magnitude). The instrument benefits from True RMS measurement for sinusoidal and non-sinusoidal waveforms and a low pass filter helps maintain stable readings. Several range options enable maximum precision and these can be selected automatically or manually.

Leakage Current Readings are displayed on the Megger DCM305E’s backlit digital screen and display options include data hold, peak hold and auto hold. Additional feedback is provided in the form of three pre-set limits (0.25, 0.5, 3.5mA) beyond which an audible alarm sounds and a visual warning is given. The 40mm jaw is designed for use on insulated and non-insulated conductors and the ergonomic form is both easy to manoeuvre and safe thanks to a raised hand guard.

The Megger DCM305E is rated as Cat III 300V and the battery lasts for roughly 60 hours. A soft carry case is provided as standard. Overall, this constitutes an excellent and versatile AC ammeter for leakage and regular current.

Megger part number: 2009-574

Megger DCM305E Key Features

  • Measure earth leakage current
  • AC current range: 100A
  • Resolution: 0.001mA
  • Accuracy: ±1%
  • True RMS measurement
  • Pre-set limits for alarms
  • 40mm jaw
  • 60-hour battery life
  • Cat III 300V

What's In The Box?

  • Megger DCM305E Earth Leakage Clamp
  • Instructions for Megger DCM305E Earth Leakage Clamp
  • Batteries
  • Soft carry case
Specification
  • Display: 6000 count
  • Measuring function: TRMS Leakage current and load current
  • Ranges: 6.000 mA / 60.00 mA / 600.00 mA / 6.000 A / 60.00 A / 100.0 A
  • Basic accuracy: ± (1.0 % + 3d)

AC Current (Range / Resolution / Accuracy)

  • 6 mA / 0.001 mA / ±(1 % reading + 8 digits)
  • 60 mA / 0.01 mA / ±(1 % reading + 8 digits)
  • 600 mA / 0.1 mA / ±(1 % reading + 8 digits)
  • 6 A / 0.001 A / ±(1 % reading + 8 digits)
  • 60 A / 0.01 A / ±(2 % reading + 10 digits)
  • 100 A / 0.1 A / ±(10 % reading + 10 digits)

Frequency response (61 ~ 400 Hz)

  • 0 ~ 10 A ±(2 % reading + 11 digits)
  • 10 ~ 50 A ±(10 % reading + 11 digits)
  • 50 ~ 100 A ±(35 % reading + 11 digits)

Low Pass Filter (Range / Resolution / Accuracy)

  • 6 mA / 0.001 mA / ±(2 % reading + 8 digits)
  • 60 mA / 0.01 mA / ±(2 % reading + 8 digits)
  • 600 mA / 0.1 mA / ±(2 % reading + 8 digits)
  • 6 A / 0.001 A / ±(2 % reading + 8 digits)
  • 60 A / 0.01 A / ±(3 % reading + 10 digits)
  • 100 A / 0.1 A / ±(12 % reading + 10 digits)

General

  • Accuracy specified at operating temperature: 23° C ± 5° C <80% RH
  • Resolution: 0.001 mA
  • Operating frequency range: 50 - 400 Hz
  • Sampling rate: 5 times / second
  • Data, auto, peak hold: User Selectable
  • Low pass filter: 50 / 60 Hz
  • Low pass filter cut-off frequency: Approximately 100 Hz with an attenuation characteristic of
  • approximately -24 dB / octave
  • Compare pre-set limits: 0.25, 0.50, 3.50 mA
  • Jaw size: 40 mm (750 mm conductor size)
  • Maximum jaw opening: 43 mm
  • Overload: “OL”
  • Auto power off: 20 minutes of inactivity
  • Operating temperature: 0 °C - 50 °C
  • Storage temperature: -20 °C - 60 °C
  • Operating Altitude: ≤2000 m
  • Temperature coefficient: 0.2 x (Spec. Accuracy) / °C, <18 °C, >28 °C
  • Power Supply: 2 x 1.5 V alkaline AAA / LR03
  • Battery life: 60 hours
  • Size: 78 mm (W) x 203 mm (H) x 42 mm (D)
  • Weight: 300 g
  • Safety: EN61010-1 CAT III 300 V
  • EMC: EN61326-1
Label Type Size Download