Megger DET3TC ART Three Pole Earth Tester

SKU: MEGGDET3TC
The Megger DET3TC Three Pole Earth Testing kit offers 2 and 3 point testing and optional Attached Rod Technique (ART).
More Info
Typically ships in 5-7 working days

Megger DET3TC ART Three Pole Earth Testing Kit

The Megger DET3TC ART Three Pole Earth Testing Kit offers a unique solution to your ground stake testing needs. The ground rod tester is rated to IP54 making it the ideal instrument for the necessary outdoor use. A large selector switch makes selection of 2 pole or 3 pole test easy even with gloves on, while the design also makes fitting shorting links for 2 pole tests a thing of the past. The Attached Rod Technique or ART is possible through use of the optional Megger ICLAMP. ART means that using the optional clamp around the ground rod connection allows the testing of the rod without the need for disconnection, leaving the earthing system intact during testing. Thus making the DET3TC a great solution for users who are concerned about the dangers and potential cost implications of disconnection of the earth spike.

A large, easy to read LCD display and well-sized test button again makes this digital ground tester particularly suited to the outdoor conditions of ground testing. In addition the DET 3TC automatically checks the connection of the P spike and C spike, indicating the status on the display. It also includes a voltmeter to allow you to measure the ground voltage. The ground tester can measure resistance from 0.01Ω through to 2000Ω and earth voltages up to 100V. To allow accurate testing in noisy environments the instrument is capable of rejecting noise of up to 40V peak to peak. This three pole earth testing kit comes protected in a tough polypropylene carry case, ideal for transportation. The Megger DET 3TC Earth Tester is designed to meet stringent safety standards and is rated CAT IV 100V.

Megger DET3TC ART Three Pole Earth Tester Key Features:

  • IP54 rated
  • 2 and 3 point testing
  • Selectable 25V or 50V output
  • Complete with lead and stake kit
  • Simple one button operation
  • Hardwearing carry case
  • Calibration certificate
  • Attached Rod Technique (ART) via optional ICLAMP
Specification
  • Ingress protection: IP54
  • C spike check: Automatic
  • P spike check: Automatic
  • Noise check: Automatic
  • Noise rejection: 40 V peak to peak
  • 2-wire test: Yes
  • 3-wire test: Yes
  • No disconnect testing (ART): Yes, with optional ICLAMP
  • Earth current range with ICLAMP: 0.5 mA to 19.9 A
  • Earth current accuracy: 5% ±3 digits
  • Resistance range: 0.01 to 2000Ω
  • Resistance accuracy: 2% ±3 digits
  • Maximum probe resistance Rp limit: 100 kΩ (50 V output voltage)
  • Maximum probe resistance Rc limit: 100 kΩ (50 V output voltage)
  • Limits reduced to 50 kΩ for 25 V output voltage
  • Limits reduced to 5 kΩ for 0.01Ω resolution on 18Ω range
  • Earth voltage range: 0 - 100 V
  • Earth voltage accuracy: 2% ±2 V AC
  • Display: LCD
  • Battery type: 8 off AA cells
  • Operating temperature range: -15 to +55ºC
  • Storage temperature range: -40 to +70ºC
  • Safety: EN61010-1 CAT IV 100 V, EN61557-1, EN61557-5
  • Dimensions: 203 x 148 x 78mm
  • Weight: 1 kg