Megger HV Tester 25 kV and 25 kV Digital

SKU: MEGGHVTESTER
  • Portable 0-25 kV DC tester for reliable insulation and cable testing
  • Built-in battery and discharge system for safe, flexible use
  • Analogue or digital versions for precise measurement
More Info
Price Available Upon Request
Made to order

Megger HV Tester 25 kV and 25 kV Digital

The Megger HV Tester 25 kV and HV Tester 25 kV Digital are portable high-voltage generators designed for DC and insulation testing of cables, joints, electrical fixtures, and similar equipment. With a variable negative DC output voltage ranging from 0 to 25 kV, these compact, lightweight, and robust instruments offer exceptional flexibility thanks to their built-in rechargeable battery, making them ideal for field testing where no external power supply is available.

Both models feature an internal discharge facility that safely and automatically discharges capacitive loads, such as shielded cables, during breakdowns or after testing. The standard model includes analogue meters, while the digital version provides precise voltage and current reading through clear digital metering. A built-in timer (1 to 30 minutes) adds further convenience and control during testing.

These instruments are suitable for testing paper-insulated and mass-impregnated cables in accordance with IEEE 400-2012 and IEC 60060-3, for electrical equipment testing as per IEEE 62.1 and IEEE 95, and for cable sheath or outer jacket testing in compliance with IEC 60502 and IEC 60229.

To arrange a demo for this product, simply click the ‘Arrange a Demo’ button at the top of the page, and to find out more about this product and the options that are available, do not hesitate to contact our team.

Key Features

  • Suitable for DC and insulation testing of cables, joints, and electrical fixtures
  • Variable negative DC output voltage from 0 to 25 kV for flexible test applications
  • Portable, lightweight, and compact design for easy field use
  • Built-in rechargeable battery enables operation without external power
  • Internal discharge facility for safe and automatic discharge of capacitive loads
  • Available with analogue or digital metering for clear and accurate readings
  • Built-in timer (1-30 minutes) for controlled test duration
  • Robust and user-friendly construction designed for reliability in demanding environments
  • Compliant with international testing standards including IEEE 400-2012, IEC 60060-3, IEEE 62.1, IEEE 95, IEC 60502, and IEC 60229

What's In The Box?

  • Megger HV Tester 25 kV
  • Rechargeable battery
  • Leather case
  • Mains lead
  • Battery lead for external Dc battery, approximately 3m
  • Ground lead, approximately 3m, for connection to station ground
  • Ground lead, approximately 3m, for connection to protective ground
  • High voltage lead, approximately 3m, with terminal
  • Operating manual
Specification
  • Input Voltage (selectable) – 115V/230V; 50/60Hz internal rechargeable battery; external batter 11…15V DC
  • Output Current – 1.5mA at maximum output voltage

Analogue Version

  • Voltage Range – 0…30kV
  • Accuracy – 1.5%
  • Output Current – 1.5mA at maximum output voltage
  • Current Range – 0.200 µA / 0…2 mA manual or automatic switching
  • Accuracy – 1.5%

Digital Version (LCD Display)

  • Voltage Range – 0…30kV (two display views)
  • Resolution – 10V
  • Accuracy – 1%
  • Current Range – 0…2mA (two display views)
  • Resolution – 1 µA
  • Accuracy – 1%
  • Battery Operating Time – Approximately 45 min at full load
  • Maximum Discharge Energy – 3000J (9.6 µF at 25kV)
  • Operating Temperature -
    -20°C…+55°C
    -29°F…+131°F
  • Storage Temperature -
    -25°C…+70°C
    -32°F…+158°F
  • Dimensions (W x H x D) – 467 x 168 x 284mm, 18.39in. x 6.61in. x 11.18in.
  • Weight – 14kg (including batteries)