Insulation Range
- Nominal Test Voltage: 1000V, 500V, 250V (d.c.)
- Measurement Range:
10kΩ - 1000MΩ on all ranges
Terminal voltage on open circuit (d.c.)
-0% +25% of rated voltage - Test Current on Load: >1mA at minimum pass values of insulation as specified in BS 761, HD 384, IEC 364 and VDE 0413 part 1
Continuity Range
- Measuring Range: 0.01Ω - 100.0Ω (0-50Ω on analogue scale)
- Open Circuit Voltage: 5V ± 1V
- Short Circuit Current: 205mA + 10mA - 5mA > 18mA (10-100Ω)
- Accuracy (at 20°C):
± 0.01Ω to 9.99Ω ± 3% ± 2 digits
10.0Ω to 99.9Ω ± 5 % ± 2 digits - Zero Offset Adjust: 0 to 9.99Ω
- Continuity Buzzer: Operates at < 2Ω
- Default Voltmeter: >25V a.c. or d.c. is applied display will operate as a voltmeter
- Range: 25V to 600V @ 50/60Hz & d.c.
Digital/Analogue Insulation and Continuity Testers
- Accuracy:
25V to 450V a.c./d.c. ± 1% ± 1 digit
450V to 600V a.c. ± 2% ± 1 digit - Test Inhibit: If more than 50V is detected, testing will be inhibited
- Auto Power Down: Auto power down operates after 10 minutes if left in standby mode
- Operating Temperature Range and Humidity:
-10°C to +55°C
93% R.H. at +40°C max - Storage Temperature Range and Humidity: -25°C to +65°C
- IP Rating: IP40
- Fuse:
500mA (F) 600V, 32x6mm
Ceramic HBC 50kA minimum
Display shows if fuse is ruptured - Over-voltage Safety Category: Meets the requirements of IEC61010-1 CAT III 600V phase to earth
- Automatic Discharge: After an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored
- Power Supply:
Battery 6 x 1.5V cells IEC LR6 type (AA Alkaline)
Rechargeable NiMH cells may be used - Battery Condition: Battery condition is constantly shown on the display as a four section bargraph
- Battery Life: 3000 consecutive tests (5 seconds per test) on any test using 2 Ah batteries
- Weight: All units 530gms ± 5%
- Dimensions: All units 195 x 98 x 40mm
- EMC: In accordance with IEC61326-1