Megger PAM410 Phase Angle Meter

SKU: MEGGPAM410
  • Measures angle between two power signals up to 359.9˚ (0.1˚ resolution)
  • Current-current, current-voltage, voltage-voltage angle measurement
  • Maximum voltage input of 500V and maximum current input of 25A
More Info
Made to order - Contact for lead time

Megger PAM410 Phase Angle Meter

The Megger PAM410 Phase Angle Meter is a sophisticated instrument that measures the phase angle between two power signals whether they are two currents, two voltages or a combination of both. The high-resolution measurement gives degree readings to 0.1˚ and the meter has a maximum voltage input of 500V and a maximum current input of 25A. This makes it suitable for checking metering installations, testing prospective relays, making comparative tests in electrical substations and checking phase angle deviation on power transformers.

The Megger PAM410’s LCD screen displays readings directly in degrees without the need for additional calculation or interpretation. The rugged case is ideal for use in challenging substation or industrial environments whilst the comparatively low weight (1.2kg) makes it easy to transport. The meter has fully rechargeable batteries and is supplied with a charger, test leads and a transport case.

Megger part number: BP-39090

Key Features

  • Measures angle between two power signals
  • Current-current, current-voltage, voltage-voltage angles
  • Measures up to 359.9˚ with 0.1˚ resolution
  • Max input voltage of 500V
  • Max current input of 25A
  • Sturdily built with rugged case
  • Alphanumeric backlit LCD display
  • Rechargeable batteries

What's In The Box?

  • Megger PAM410 Phase Angle Meter
  • Test lead set
  • Battery charger
  • Transport case
Specification

Environment

  • Application field: The instrument is intended for use in high-voltage substations and industrial environments.
  • Operating temperature: -10°C to +50°C (14°F to +122°F)
  • Storage & transport temperature: -40°C to +70°C (-40°F to +158°F)
  • Humidity: 5% – 95% RH, non-condensing
  • Altitude: < 2000 m above sea level

CE-marking

  • EMC: 2004/108/EC
  • LVD: 2006/95/EC

General

  • Measurement category CAT III 500 V / CAT IV 300 V
  • Enclosure class: IP21
  • Power supply: Rechargeable batteries
  • Mains adapter: 100–240 V AC, 50/60 Hz
  • Adapter output voltage: 9 V DC
  • Power consumption: 10 W (max)
  • Instrument dimensions: 260 x 140 x 55 mm (except handle) (10.2” x 5.5” x 2.2”)
  • Transport case dimensions: 390 x 300 x 140 mm (15.4” x 11.8” x 5.5”)
  • Weight: 1.2 kg (2.6 lbs) / 3.5 kg (7.7 lbs) with accessories and transport case
  • Test lead set, with 4 mm stackable safety plugs: Black 2 x 2 m (6.6 ft), 2.5 mm2 / Red 2 x 2 m (6.6 ft), 2.5 mm2
  • Display: Alpha numerical LC display with backlight

Measurement section (Phase angle)

  • Range: 0 – 359.9°(2–500 V and 0.15–25 A)
  • Type of phase angle measurement: Current-current, voltage-voltage and current-voltage
  • Waveform: Sinusoidal
  • Resolution: 0.1°
  • Inaccuracy: ±0.5° at >10% of voltage/current range; ±1° at 2–10% of voltage/current range; ±2° at 1–2% of voltage/current range
Label Type Size Download
pdf Megger PAM410 Datasheet pdf 137.6 KB Download