Megger PAM410 Phase Angle Meter

SKU: MEGGPAM410

Never Beaten On Price

 

We’re always working hard to give you the best possible price, but if you find it cheaper somewhere else, we’ll endeavour to match the price.

 

Call 0113 248 9966 or contact us online

Made to order - Contact for lead time
Need Some Help From Our Experts? chevron-right chevron-down

We're always happy to offer help, information & advice to find the right instrument for you, so please get in touch.

 

To speak to our sales team, call us on 0113 248 9966, use our Live Chat service or contact us online.

Members earn 4515 reward points chevron-right chevron-down

Use reward points to get money off future purchases.

 

Please note: Customers must be signed into their account to be elegible. Find out more about reward points here.

FREE Delivery & 60 Day Returns chevron-right chevron-down

We offer FREE standard delivery on all orders over £249, with a range of next-day options also available on many items.

 

Find out more on our delivery information page.

Key Features
  • Measures angle between two power signals up to 359.9˚ (0.1˚ resolution)
  • Current-current, current-voltage, voltage-voltage angle measurement
  • Maximum voltage input of 500V and maximum current input of 25A

Megger PAM410 Phase Angle Meter

The Megger PAM410 Phase Angle Meter is a sophisticated instrument that measures the phase angle between two power signals whether they are two currents, two voltages or a combination of both. The high-resolution measurement gives degree readings to 0.1˚ and the meter has a maximum voltage input of 500V and a maximum current input of 25A. This makes it suitable for checking metering installations, testing prospective relays, making comparative tests in electrical substations and checking phase angle deviation on power transformers.

The Megger PAM410’s LCD screen displays readings directly in degrees without the need for additional calculation or interpretation. The rugged case is ideal for use in challenging substation or industrial environments whilst the comparatively low weight (1.2kg) makes it easy to transport. The meter has fully rechargeable batteries and is supplied with a charger, test leads and a transport case.

Megger part number: BP-39090

Key Features

  • Measures angle between two power signals
  • Current-current, current-voltage, voltage-voltage angles
  • Measures up to 359.9˚ with 0.1˚ resolution
  • Max input voltage of 500V
  • Max current input of 25A
  • Sturdily built with rugged case
  • Alphanumeric backlit LCD display
  • Rechargeable batteries

What's In The Box?

  • Megger PAM410 Phase Angle Meter
  • Test lead set
  • Battery charger
  • Transport case
Show Trustpilot Reviews
Specification
No

Environment

  • Application field: The instrument is intended for use in high-voltage substations and industrial environments.
  • Operating temperature: -10°C to +50°C (14°F to +122°F)
  • Storage & transport temperature: -40°C to +70°C (-40°F to +158°F)
  • Humidity: 5% – 95% RH, non-condensing
  • Altitude: < 2000 m above sea level

CE-marking

  • EMC: 2004/108/EC
  • LVD: 2006/95/EC

General

  • Measurement category CAT III 500 V / CAT IV 300 V
  • Enclosure class: IP21
  • Power supply: Rechargeable batteries
  • Mains adapter: 100–240 V AC, 50/60 Hz
  • Adapter output voltage: 9 V DC
  • Power consumption: 10 W (max)
  • Instrument dimensions: 260 x 140 x 55 mm (except handle) (10.2” x 5.5” x 2.2”)
  • Transport case dimensions: 390 x 300 x 140 mm (15.4” x 11.8” x 5.5”)
  • Weight: 1.2 kg (2.6 lbs) / 3.5 kg (7.7 lbs) with accessories and transport case
  • Test lead set, with 4 mm stackable safety plugs: Black 2 x 2 m (6.6 ft), 2.5 mm2 / Red 2 x 2 m (6.6 ft), 2.5 mm2
  • Display: Alpha numerical LC display with backlight

Measurement section (Phase angle)

  • Range: 0 – 359.9°(2–500 V and 0.15–25 A)
  • Type of phase angle measurement: Current-current, voltage-voltage and current-voltage
  • Waveform: Sinusoidal
  • Resolution: 0.1°
  • Inaccuracy: ±0.5° at >10% of voltage/current range; ±1° at 2–10% of voltage/current range; ±2° at 1–2% of voltage/current range
Label Type Size Download