Metrel MI3152 EurotestXC EVSE Pro Test Kit

SKU: METREVSEPROKITENTRY
  • An advanced kit specifically designed for testing electric vehicle charging points
  • Includes the downloadable, Bluetooth-enabled Metrel MI3152 Eurotest XC MFT
  • Metrel A1532 Adaptor allows state-by-state testing on charging points
  • Upgradeabel and futureproof Multifuncttion Tester
More Info
£1,678.80 £1,399.00
In Stock - Available Next Day
Choose Your Free Gift

Metrel MI3152 EurotestXC EVSE Pro Test Kit

The Metrel MI3152 EurotestXC EVSE Pro Test Kit is an advanced option for those looking to undertake work on electric vehicle charging points as well as other electrical installations. It features the advanced Metrel MI3152 Eurotest XC Multifunction Tester with a choice of either the Metrel A1532 or A1532XA EVSE Adaptors. 

Metrel MI3152 EurotestXC Multifunction Tester

The Metrel MI3152 Eurotest XC is one of Metrel’s most advanced instruments, featuring a wide range of tests plus intuitive operation and smart functionality. The testing facilities on the Metrel MI3152 make it suitable for all manner of electrical contractors. It is capable of testing continuity on inductive loads (7mA) and R1+R2 or R2 (200mA) as well as insulation resistance with test voltages from 50V to 1000V DC.

Loop and line impedance testing is also possible and various types of RCDs can be tested (general, selective, type AC, A, F, B and B+). Finally, measurement functions include leakage current, TRMS voltage, phase rotation, frequency, and light/lux levels (ideal for checking emergency lighting). Note that some of these features will require additional adaptors and accessories. Please contact our sales team for prices and information.

Aside from its advanced testing capabilities, the Metrel MI3152 also boasts intuitive operation via a vibrant colour touchscreen. Built-in help screens offer advice to the user and fully updated BS7671 tables allow the tester to provide a PASS/FAIL indication for loop test measurements. It is possible to programme specific test sequences and the large internal memory is downloadable via Bluetooth or USB to a PC for further analysis.

Metrel A1532 / A1532XA EVSE Adaptor

The Metrel A1532 Electric Vehicle Charging Point Adaptor allows the user to test both the functionality and the safety of a charging point when used in conjunction with the Metrel MI3152XC Tester. It enables the user to simulate the effect of a vehicle attached to a charging point in various charging states. One of the most important aspects of the adaptor is that there is no need to disassemble the charging point to test all of the various aspects.

A particularly useful feature of the Metrel EVSE Pro Kit is the Metrel MI3152’s automated test sequence which can be used along with the Metrel A1532. This tests the charging point on a comprehensive state-by-state basis at the push of a button. The MFT’s type B RCD test function is also particularly useful for testing charging points.

In addition to these features the A1532XA model allows Diode Short Error Simulation, PE Open Error Simulation and CP Short Error Simulation (E State) as well as Load Test up to 13 A.

Differences between the A1532 and A1532XA EV Charging Station Adaptor

  A 1532 EVSE Adadpter A 1532 XA EVSE Adadpter
Features
EVSE Mode
AUTOSEQUENCES
EVSE Measurements
Proximity Pilot 0-64 A
Control Pilot States Settings
Line Impedance for Charging Station
Fault Loop Impedance for Charging Station
Functional Test of Proximity Pilot
Functional Test of Control Pilot
Isolation Test for Charging Station
1-Phase Charging Station Testing
1-Phase Test Through Socket
3-Phase Charging Station Testing
Diode Short Error Simulation -
PE Open Error Simulation -
CP Short Error SImulation (E State) -
Load Test up to 13 A -
Building Facilities
EVSE Construction and Testing
Standards Applied
Building LV Installation
EISinsp Competences:
Low Voltage Electrical Installation
Safety Inspection
EISc Competences:
Low Voltage Electrical Installation
Safety for Contractors and Maintainers
IEC/EN 61557 Electrical Safety
in Low Voltage Distribution Systems up to 1000V AC and 1500V DC
- Equipment for testing, measuring or monitoring of protective measures - series
Standards Applied
Electrical Vehicle Supply Equipment
EVSE Competences:
Electrical Vehicle Supply
Equipment Safety
IEC/EN 61851 Electric Vehicle
Conductive Charging System

What's In The Box?

  • Metrel MI3152 Eurotest XC Multifunction Tester
  • Metrel A1532 EVSE Charging Point Adaptor
  • Three-wire test lead set
  • Three test probes
  • Three crocodile clips
  • Mains plug test lead
  • Neck strap
  • Carry case
Specification

CONTINUITY

Test Current: 7 mA, 2-wire

  • Ranges: 0.00 Ω ... 19.99 Ω; 20.0 Ω ... 1999 Ω
  • Resolution: 0.1 Ω; 1 Ω 
  • Accuracy: ±(5 % of r. + 3 digits)

Test Current: 200 mA 2-wire

  • Ranges: 0.00 Ω ... 19.99 Ω; 20.0 Ω ... 199.9 Ω; 200.0 Ω ... 1999 Ω
  • Resolutions: 0.01 Ω; 0.1 Ω; 1 Ω
  • Accuracy: ±(3 % of r. + 3 digits); ±(5 % of r.); ±(5 % of r.)

INSULATION RESISTANCE

Test Voltage: 50/100/250 V

  • Ranges: 0.00 MΩ ... 19.99 MΩ; 20.0 MΩ ... 99.9 MΩ; 100.0 MΩ ... 199.9 MΩ
  • Resolutions: 0.01 MΩ; 0.1 MΩ
  • Accuracy: ±(5 % of r. + 3 digits); ±(10 % of r.); ±(20 % of r.)

Test Voltage: 500/1000 V

  • Ranges: 0.00 MΩ ... 19.99 MΩ; 20.0 MΩ ... 199.9 MΩ; 200 MΩ ... 999 MΩ
  • Resolutions: 0.01 MΩ; 0.1 MΩ; 1 MΩ
  • Accuracy: ±(5 % of r. + 3 digits); ±(5 % of r.); ±(10 % of r.)

RCD

RCD Uc

  • Ranges: 0.00 V ... 19.99 V; 20.0 V ... 99.9 V
  • Resolution: 0.1 V 
  • Accuracy: (-0%/+15%) ofr .± 10 digits; (-0%/+15 %) of r.

RCD (t),

  • Ranges: 0.00 ms ... 40.0 ms; 0.0 V ... max.time 
  • Resolution: 0.1 ms 
  • Accuracy: ±1 ms; ±3 ms

RCD I Ramp

  • Ranges: 0.2xI∆N ... 1.1xI∆N (AC); 0.2xI∆N ... 1.5xI∆N (A), I∆N ≥30 mA); 0.2xI∆N ... 2.2xI∆N (A), I∆N <30 mA); 0.2xI∆N ... 2.2xI∆N (B)
  • Resolution: 0.05xI∆N 
  • Accuracy: ±0.1xI∆N

IMPEDANCE

Zline L-L, L-N Ipsc

  • Ranges: 0.00 Ω ... 9.99 Ω; 10.0 Ω ... 99.9 Ω; 100 Ω ... 999 Ω; 1.00 kΩ ... 9.99 kΩ
  • Resolutions: 0.01 Ω; 0.1 Ω; 1 Ω; 10 Ω
  • Accuracy: ±(5 % of r. + 5 digits); ±(10 % of r.)

Zloop L-PE, Ipfc

  • Ranges: 0.00 Ω ... 9.99 Ω; 10.0 Ω ... 99.9 Ω; 100 Ω ... 999 Ω; 1.00 kΩ ... 9.99 kΩ
  • Resolutions: 0.01 Ω; 0.1 Ω; 1 Ω; 10 Ω
  • Accuracy: ±(5 % of r. + 5 digits); ±(10 % of r.)

VOLTAGE TRMS

  • Range: 0 … 550 V 
  • Resolution: 1 V
  • Accuracy: ±(2 % of r. + 2 digits)
  • Frequency ranges: 0.00 Hz .. 9.99 Hz; 10.0 Hz ... 499.9 Hz
  • Frequency resolution: 0.01 Hz; 0.1 Hz 
  • Accuracy: ±(0.2 % of r. + 1 digits)

CURRENT

TRMS, AC with A 1018

  • Ranges: 0.0 mA ... 99.9 mA; 100 mA ... 999 mA; 1.00 A ... 19.99 A
  • Resolutions: 0.1 mA; 1 mA; 0.01 A
  • Accuracy: ±(5 % of r. + 5 digits); ±(3 % of r. + 3 digits); ±(3 % of r.)

TRMS, AC with A 1019

  • Ranges: 0.0 mA ... 99.9 mA; 100 mA ... 999 mA; 1.00 A ... 19.99 A
  • Resolutions: 0.1 mA; 1 mA; 0.01 A
  • Accuracy: Indicative; ±(5 % of r.); ±(3 % of r.)

TRMS, AC/DC with A 1391, range=40 A

  • Ranges: 0.00 A ... 1.99 A; 2.00 A ... 19.99 A; 20.0 A ... 39.9 A
  • Resolutions: 0.01 A; 0.01 A; 0.1 A
  • Accuracy: ±(3 % of r. + 3 digits); ±(3 % of r.); ±(3 % of r.)

TRMS, AC/DC with A 1391, range = 300 A

  • Ranges: 0.00 A ... 19.99 A; 20.0 A ... 39.9 A; 40.0 A ... 299.9 A
  • Resolutions: 0.01 A; 0.1 A; 0.1 A
  • Accuracy: Indicative; indicative; ±(3 % of r. + 5 digits)

EARTH RESISTANCE

3 wire

  • Ranges: 0.00 Ω ... 19.99 Ω; 20.0 Ω ... 199.9 Ω; 200.0 Ω ... 9999 Ω
  • Resolutions: 0.01 Ω; 0.1 Ω; 1 Ω
  • Accuracy: ±(5 % of r. + 5 digits)

2 clamp

  • Ranges: 0.00 Ω ... 19.99 Ω; 20.0 Ω ... 30.0 Ω; 30.1 Ω ... 39.9 Ω
  • Resolutions: 0.01 Ω; 0.1 Ω; 0.1 Ω
  • Accuracy: ±(10 % of r. + 10 digits); ±(20 % of r.); ±(30 % of r.)

Specific earth resistance

  • Ranges: 0.0 Ωm … 99.9 Ωm; 100 Ωm ... 999 Ωm; 1.00 kΩm ... 9.99 kΩm; 10.0 kΩm ... 99.9 kΩm; 100 kΩm ... 9999 kΩm
  • Resolutions: 0.1 Ωm; 1 Ωm; 0.01 kΩm; 0.1 kΩm; 1 kΩm
  • Accuracy: ±(5 % of r.) for Re 1 Ω … 1999kΩ; ±(10 % of r.) for Re 2 kΩ … 19.99kΩ; ±(20 % of r.) for Re > 20 kΩ

FIRST FAULT LEAKAGE CURRENT

  • Range: 0.0 mA ... 19.9 mA 
  • Resolution: 0.1 mA 
  • Accuracy: ±(5 % of r. + 3 digits)

IMD TEST

  • Threshold indicative insulation resistance 
  • Range: 5 … 640 kΩ 
  • Resolution: 5 kΩ 
  • Accuracy: Indicative values, up to 128 steps

ILLUMINANCE

Type B

  • Ranges: 0.01 lux ... 19.99 lux; 20.0 lux ... 199.9 lux; 200 lux ... 1999 lux; 2.00 klux ... 19.99 klux
  • Resolutions: 0.01 lux; 0.1 lux; 1 lux; 10 lux
  • Accuracy: ±(5 % of r. + 2 digits); ±(5 % of r.)

Type C

  • Ranges: 0.01 lux ... 19.99 lux; 20.0 lux ... 199.9 lux; 200 lux ... 1999 lux; 2.00 klux ... 19.99 klux
  • Resolutions: 0.01 lux; 0.1 lux; 1 lux; 10 lux
  • Accuracy: ±(10 % of r. + 3 digits); ±(10 % of r.)


GENERAL

  • Power supply: 9 VDC (6x1.5 V battery or accu, size AA)
  • Overvoltage category: 1000 V DC CAT II; 600 V CAT III; 300 V CAT IV
  • Protection class: Double insulation
  • COM port: BT, USB, RS232
  • Weight: 1.3 kg
  • Size ( l x h x w ): 230 x 103 x 115 mm