DiLOG DL9130EV Multifunction Tester

SKU: DILOGDL9130EV
  • Top of the range Multifunction Tester from DiLOG with complete EVSE testing capabilities
  • Auto sensing high current 2 & 3 wire loop test
  • Auto EV Test Sequences and Auto Start Loop & Continuity Tests
More Info
In Stock - Available Next Day
Choose Your Free Gift

DiLOG DL9130EV Advanced 18th Edition Multifunction Tester

The DiLOG DL9130EV Advanced 18th Edition Multifunction Tester is specifically designed to support those electricians who offer EV charge point installation services. Amongst its features, the DL9130EV sports some new functionalities that are critical in ensuring safe EVSE installation including full 6mA pure DC test for RDC-DD verification, EV testing sequence for verifying DC protection and type A RCD protection. In addition, the newly introduced Rmax and Zmax features will automatically capture maximum values for R1+R2 continuity tests and Zs tests respectively and display them upon test completion.

Also new within DiLOG’s 18th Edition MFT range is the inclusion of a colour RGB display, able to visually indicate potential pass/fail conditions. The screen presents values using large and clear digits and is fully backlit. The tactile rotary dial and sizeable function buttons allow for easy option/mode selection, even when using a gloved hand.

An auto sensing intelligent high current 2 and 3 wire loop test enables this MFT to detect when users are performing a 2 wire or 3 wire loop/PSCC measurement without the need for mode selection. Likewise, the auto start continuity test feature provides additional automation for further ease of use. Insulation measurement are possible using 250, 500 and 1000V test voltages.

The perfect tool for EV installation testing, this MFT offers great value and a variety of innovative features ready for use and allows for the safety and operational performance of each install to be assessed in line with BS EN 61557 standards.

Below, you will find a comparison table outlining the key differences between recent DiLOG MFT models, helping you to make the most informed purchasing decision.

  DL9110 DL9118 DL9120 DL9130EV
Continuity Test
15 mA/200mA Selectable Current      
R Max (Max R1+R2 recording)      
Insulation Test 250V, 500V 250V, 500V, 1000V 250V, 500V, 1000V 250V, 500V, 1000V
Loop Test (3-wire no-trip)
2-Wire Loop Test    
Auto Start Loop & Continuity
Auto Start PFC/PSC (L-PE/L-N)    
Z Max      
PFC and PSC Fault Current(L-PE/L-N)
Phase-Phase Line Test (L-L)  
RCD Test (AC, A, S-type)
Auto RCD Test
RCD Ramp Test
6 mA RDC-CC (EVSE)      
Auto EV RCD Test Sequence      
RCD Test Type B    
Phase Rotation  
Intelligent Full Range Protection
Colour RGB display
Colour change indicates error
Remote Test Probe Include    
Includes calibration certificate

What's In The Box?

  • Di-LOG Advanced EV 18th Edition Multifunction Tester
  • Padded Neck Strap
  • Professional toolbox style carry case
  • Mains leads
  • 1.2M blue test lead
  • 1.2M red test lead
  • 1.2M green test lead
  • Blue crocodile clip
  • Red crocodile clip
  • Green crocodile clip
  • MN1500 (AA) 1.5v batteries x 6
  • Operating instruction manual
  • Calibration certificate
Specification

    Voltage

    • Display range: 0V - 480V
    • Measuring range: 0V - 480V
    • Resolution: 1V
    • Voltage accuracy: +/- 5% +/- 2digits
    • Frequency range: 45.0Hz – 65.0HzV
    • Frequency accuracy: +/- 1.0Hz

    Continuity

    • Display Range (200mA): 0.01Ω to 2000Ω
    • Measuring Range (200mA): 0.10Ω to 2000Ω
    • Accuracy: +/- 2% +/- 5 digits
    • Resolution: 0.01Ω to 19.99Ω, 20.0Ω to 199.9Ω, 200Ω to 2000Ω
    • Test voltage: >4Vdc >25Vdc Open Circuit
    • Test current: >200mA
    • Display Range (15mA): 0.01Ω to 200Ω
    • Accuracy: +/- 2% +/- 5 digits
    • Resolution: 0.01Ω to 19.99Ω, 20.0Ω to 199.9Ω/>4Vdc >25Vdc Open Circuit/>15mA
    • Compliance: IEC61557-4 and IEC61557-10

    Insulation

    • Display range: 0.01MΩ to 200MΩ
    • Display range: 0.05MΩ to 200MΩ
    • Insulation: +/-5% +/-5 digits
    • Resolution: 0.01MΩ to 1.99MΩ, 2.0MΩ to 19.9MΩ, 20MΩ to 200MΩ
    • Alarm warning: <1MΩ Screen & Audible
    • Test voltage: 250/500/1000V
    • Test voltage specification: -0% +20% (open circuit)
    • Test current: 1mA into UN (1000Ω/V)
    • Compliance: IEC61557-2 and IEC61557-10

    No Trip Loop Impedance

    • Supply voltage: 195-253V, 45Hz – 65Hz
    • Display range: 0.01Ω to 2000Ω
    • Measuring range: 1.00 to 1999Ω (non-trip)
    • Accuracy: +/-5% +/-12 digits (to 20Ω) +/-5% +/-5 digits (to 2000Ω)
    • Resolution: 0.01Ω to 9.99Ω, 10.0Ω to 99.9Ω, 100Ω to 2000Ω
    • Test current: <15mA RMS

    High Current Loop Impedance

    • Supply voltage: 195-253V, 45Hz – 65Hz
    • Display range: 0.01Ω to 2000Ω
    • Measuring range: 0.10Ω to 1999Ω (high current)
    • Accuracy: +/-5% +/-12 digits (to 20Ω) +/-5% +/-5 digits (to 2000Ω)
    • Resolution: 0.01Ω to 9.99Ω, 10.0Ω to 99.9Ω, 100Ω to 2000Ω
    • Test current: 3A RMS

    Loop Test PFC Measurement

    • Display range: 0.1A to 26.0kA
    • Accuracy: +/-5%  +/-5 digits
    • Resolution: 0.1A to 999.9A, 1.0kA to 26.0kA

    High Current Line Impedance

    • Display range: 0.01Ω to 2000Ω
    • Measuring range: 0.10Ω to 2000Ω
    • Accuracy: +/-5% +/-5 digits
    • Resolution: 0.01Ω to 9.99Ω, 10.0Ω to 99.9Ω, 100Ω to 2000Ω
    • Supply voltage: 195V – 253V, 328V – 480V
    • Test current: 3A RMS Peak

    Line Test PSC Measurement

    • Range: 0.1A to 26.0kA
    • Accuracy: +/-5%  +/-5 digits
    • Resolution: 0.1A to 999.9A, 1.0kA to 26.0kA
      • RCD Trip Time Test

        • Supply voltages: 195-253V, 45Hz – 65Hz
        • Nominal test current: 10mA/30mA/100mA ( ½ , 1, 5 I∆n), 300mA/500mA ( ½, 1 I∆n), Variable Mode
        • Variable RCD test: 1mA – 500mA
        • Test current accuracy: -0% +10% at I∆n and 5I∆n, -0% +10% at ½ I∆n
        • Trip time ranges: 0 to 2000ms ½ I∆n, 0ms - 300ms I∆n general, 0ms - 500ms I∆n selective, 0 to 40ms 5 I∆n
        • Trip time accuracy: +/- 5% +/- 2 digits
        • Nominal test current: 10mA/30mA/100mA ( ½ , 1, 5 I∆n), 300mA/500mA ( ½, 1 I∆n)
        • Compliance: IEC61557-6 and IEC61557-10

        RDC-DD Trip Time Test

        • 195-253V, 45Hz – 65Hz
        • 6mA
        • -0% +10%
        • 0 to 10000 I∆n
        • +/- 5% +/- 2 digits
        • 2mA – 10mA
        • IEC61557-6 and IEC61557-10

        RDC (Ramp) Trip Current Test

        • Range: 0.5 I∆n to 1.1 I∆n
        • Accuracy: +/-5% of the expected current
        • Step Size: 0.1*∆n
        • Step duration: 300ms
        • Compliance: IEC61557-6 and IEC61557-10

        Additional Data

        • Weight: 1360g
        • Dimensions: Width 236mm, Depth 130mm, Height 91mm
Kit Option
DiLOG DL9130EV Multifunction Tester & EVSE Adaptor Kit
£999.00
In Stock - Available Next Day