Martindale HPAT400 PAT Test Kit B is based around the Martindale HPAT400 PAC Checker, a useful instrument for those with low volume testing commitments in offices, residential settings and environments where power tools are used.

The Martindale HPAT400 has a 200mA earth bond test, 500V insulation resistance test, leakage current test and polarity check. These tests are initiated in automatic test sequences for Class I appliances, Class II appliances and power leads. All the user needs to do is correctly identify the appliance and then connect the tester.

As a PAC checker, readings are not given for each test and instead PASS/FAIL limits are given for each test according to pre-set limits saved within the Martindale HPAT400. An overall result for the test is also provided on screen but does mean that the tester is unsuitable for long extension leads.

Martindale HPAT400 Kit B contains a set of 110V adaptors for industrial appliances and leads, typically power tools; extension lead and IEC adaptors, a PAT register book, a PAT certificate pad, and a socket tester. Full contents are listed below.

Martindale HPAT400 Kit B Includes:

  • Martindale HPAT400 PAC Checker
  • PAT Certificate Pad
  • PAT Register Book w/ Frequency of Inspection
  • 110V Appliance Adaptor
  • 110V Extension Lead Adaptor
  • IEC Clover Leaf Adaptor
  • Martindale CP501 Socket Tester
  • 1000 Pass Labels
  • 200 Fail Labels
  • 250 PassWrap Cable Labels
  • 250 Tuff Tag Pass Cable Labels
  • Earth Bond Test Lead
  • 230V Extension Lead Adaptor
  • Mains Lead
  • 6 x Rechargeable Batteries
  • HPAT400 Carry Case
  • Portable Appliance Tester Kit Carry Case
  Kit A Kit B Kit C Kit D
Martindale HPAT400 PAT Tester
Microwave Leakage Detector    
50 Microwave Emissions Labels    
PAT Certificate Pad    
PAT Register Book w/ Frequency of Inspection
IEC Clover Leaf Adaptor  
Martindale CP501 Check Plug  
1000 Pass Labels
200 Fail Labels
250 PassWrap Cable Labels
250 Tuff Tag Cable Labels    
Earth Bond Test Lead
Mains Lead
230V Extension Lead Adaptor
110V Appliance Adaptor    
110V Extension Lead Adaptor    
Rechargeable Batteries
HPAT400 Carry Case
Portable Appliance Tester Kit Carry Case  

What's In The Box?

  • Martindale HPAT400 PAT Tester
  • PAT Certificate Pad
  • PAT Register Book w/ Frequency of Inspection
  • 110V Appliance Adaptor
  • 110V Extension Lead Adaptor
  • IEC Clover Leaf Adaptor
  • Martindale CP501 Socket Tester
  • 1000 Pass Labels
  • 200 Fail Labels
  • 250 PassWrap Cable Labels
  • 250 Tuff Tag Pass Cable Labels
  • Earth Bond Test Lead
  • 230V Extension Lead Adaptor
  • Mains Lead
  • 6 x Rechargeable Batteries
  • HPAT400 Carry Case
  • Portable Appliance Tester Kit Carry Case
Specification

EARTH CONTINUITY

  • Test voltage: 4V DC (into open circuit) Test current: 200mA DC (into short circuit)
  • Accuracy: ± 0.03Ω
  • Pass limits: Lead ≤ 0.20 Ω = PASS; Class I ≤ 0.20 Ω = PASS

INSULATION

  • Fixed voltage: >500V DC at 1mA (< 625V DC into open circuit)
  • Test current: 1.5mA (into short circuit)
  • Accuracy: ± 0.1MΩ
  • Pass limits: Lead: ≥ 1.0 MΩ; Class I: ≥ 1.0 MΩ; Class II: ≥ 2.0 MΩ

FUSE CHECK

  • Test voltage: 4V DC (into open circuit)
  • Test current: 200mA DC (into short circuit)
  • Pass level: >2mA

GENERAL

  • Overload protection: 300V AC/DC