Megger DET4TC2 Professional Earth Testing Kit 1000-404

SKU
MEGGDET4TC2KIT
  • Features Megger DET4TC2 Earth Tester as primary instrument
  • Enhances capabilities with clamps for ART and stake-less testing
  • Includes additional professional ground testing kit
More Info
inc VAT £2,094.00 ex VAT £1,745.00
Typically ships in 5-7 working days
 

Product Details

Megger DET4TC2 Professional Earth Testing Kit

The Megger DET4TC2 Professional Earth Testing Kit features the sophisticated Megger DET4TC2 Earth Tester as its primary device alongside several accessories which considerably enhance ground-testing capabilities. The instrument itself can perform one-, two-, and three-pole testing; leakage current measurement; and ground noise voltage measurement over impressive ranges. The device has voltage outputs of 25V or 50V with a range of different currents and frequencies which are all easily substituted, even with gloves. The Megger DET4TC2 Earth Tester is weatherproof to IP54 standard and meets all relevant safety standards including IEC61010-1 Cat IV 100V. It is powered by eight commonly available AA batteries so it is extremely practical.

The Megger DET4TC2 Professional Kit enhances the earth tester’s capabilities on several levels. Firstly, as with the Megger DET4TC2 Earth Testing Kit with Clamps, the ICLAMP allows ART testing and the VCLAMP permits stake-less testing when conditions do not allow the user to drive stakes into the ground. In addition, the supplied field calibration check for the clamps and the instrument helps safeguard accuracy.

The included professional ground testing kit provides everything the user might need to carry out comprehensive ground tests with the Megger DET4TC2. It includes two 50m wires, two 30m wires, four auger stakes, a tape measure and hard carry case. This is all provided on top of the standard stake and wire kit so the user’s measurement options are greatly increased. All in all, the Megger DET4TC2 Kit helps the user get the most out of his or her Megger DET4TC2 Earth Tester when carrying out accurate, comprehensive ground testing.

Megger part number: 1000-404

Key Features

  • Megger DET4TC2 Earth Tester
  • Professional ground testing kit including 2 x 50m wires, 2 x 30m wires, four auger stakes, a tape measure and hard carry case
  • Standard hard carry case
  • Standard stake and wire kit (15m, 10m, 10m, 3m)
  • ICLAMP for ART testing
  • VCLAMP for stake-less testing
  • Field calibration check for instrument and clamps
  • Right angle terminal adaptors for connecting bare wires to terminals
  • Calibration certificate
What's In The Box?
  • Megger DET4TC2 Earth Tester
  • Standard hard carry case
  • Standard stake and wire kit (15m, 10m, 10m, 3m)
  • ICLAMP for ART testing
  • VCLAMP for stake-less testing
  • Field calibration check for instrument and clamps
  • Right angle terminal adaptors for connecting bare wires to terminals
  • Calibration certificate

PLUS professional ground testing kit including:

  • 2 x 50m wires
  • 2 x 30m wires
  • 4 x auger stakes
  • 1 x tape measure
  • 1 x hard carry case
More Information
Specification
  • Ingress protection: IP54
  • C stake, P stake and Noise check: Automatic
  • Noise rejection: 40 V pk to pk
  • 2-wire, 3-wire, 4-wire test: Yes, no shorting links required
  • No disconnect testing (ART): Yes, with ICLAMP
  • Stakeless measurement: Yes, with ICLAMP and VCLAMP

Instrument output

  • Voltage: ±25 V or ±50 V at 94 Hz, 105 Hz, 111 Hz and 128 Hz
  • Current: 4.5 mA or 0.45 mA or 0.045 mA
  • Ground current range with clamp: 0.5 mA to 19.9 A
  • Ground current accuracy: 5% ±3 digits
  • Ground voltage range: 0 to 100 V ac
  • Ground voltage accuracy: 2% ±2 V

Resistance ranges

  • 2, 3, 4 pole: 0.01 Ω to 200 kΩ
  • ART: 0.01 Ω to 200 kΩ
  • Stakeless: 0.01 Ω to 200 Ω

Resistance accuracy

  • 2P measurements: 2% ±3 digits
  • 3P measurements: 2% ±3 digits
  • 4P measurements: 2% ±3 digits
  • ART measurements: 5% ±3 digits
  • Stakeless measurements: 7% ±3 digits

Maximum probe resistance

  • Rp limit: 200 kΩ (50 V output voltage)
  • Rc limit: 200 kΩ (50 V output voltage)
  • Limits reduced to 100 kΩ for 25 V output voltage
  • Limits reduced to 5 kΩ for 0.01 Ω resolution
  • Display: 3.5” digit high contrast liquid crystal, backlit
  • Battery type: DET4TC2: 8 off AA (LR6) cells
  • Operating temperature range: -15 °C to +55 °C / 5 °F to 131 °F
  • Storage temperature range: -40 °C to +70 °C / -40 °F to 158 °F

Safety

  • Complies with the requirements of IEC61010-1 100V CAT IV between terminal pairs.*

EMC

  • In accordance with IEC61326-1

Standards Compliance

  • Complies with the requirements of KEMA K85B
  • Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective measures”.
  • Part 1 - General requirements
  • Part 5 - Resistance to earth
  • Dimensions: 203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in)
  • Weight: 1kg (2.2lb)

*The CAT IV 100 V rating is dependant on the use of a lead set of
at least this rating, for example the optional two wire lead set part
number 1001-858.